H3 Multi-Function Analog Input Settings

H3-oo

Setting

Function

Description

Page

6

DC Injection Braking current

10 V = Drive rated current

228

7

Overtorque/undertorque

detection level

10 V = Drive rated current (V/f)

228

8

Stall Prevention level during run

10 V = Drive rated current

228

9

Output frequency lower limit level

10 V = E1-04 (maximum output frequency)

228

B

PID feedback

10 V = 100%

228

C

PID setpoint

10 V = 100%

228

D

Frequency bias

10 V = E1-04 (maximum output frequency)

228

E

Motor Temperature (PTC Input)

10 V = 100%

Note:

A 12 kΩ resistor must be connected between one of the terminals A1, A2,

or A3 and V+ for PTC functionality. Connect the 12 kOhm resistor to the

same terminal as the PTC input. Do not connect terminals V+ to AC, or

damage to the drive may result.

229

16

Differential PID feedback

10 V = 100%

229

17

Motor Thermistor (NTC)

10 V = -9 °C

0 V = 234 °C

229

1F

Through mode

Set this value when using the terminal in the pass-through mode.

229

25

Secondary PI Setpoint

10 V = S3-02 (maximum output frequency)

229

26

Secondary PI Feedback

10 V = S3-02 (maximum output frequency)

229

u

H4: Analog Outputs

No.

(Addr.

Hex)

Name

Description

Values

Page

H4-01

(41D)

Multi-Function Analog

Output Terminal FM

Monitor Selection

Selects the data to be output through multi-function analog output terminal

FM.

Set the desired monitor parameter to the digits available in Uo-oo.

For example, enter “103” for U1-03.

Default: 102

Range: 000 to 999

229

H4-02

(41E)

Multi-Function Analog

Output Terminal FM Gain

Sets the signal level at terminal FM that is equal to 100% of the selected

monitor value.

Default: 100.0%

Min.: -999.9

Max.: 999.9

229

H4-03

(41F)

Multi-Function Analog

Output Terminal FM Bias

Sets the signal level at terminal FM that is equal to 0% of the selected monitor

value.

Default: 0.0%

Min.: -999.9

Max.: 999.9

229

H4-04

(420)

Multi-Function Analog

Output Terminal AM

Monitor Selection

Selects the data to be output through multi-function analog output terminal

AM.

Set the desired monitor parameter to the digits available in Uo-oo.

For example, enter “103” for U1-03.

Default: 103

Range: 000 to 999

229

H4-05

(421)

Multi-Function Analog

Output Terminal AM Gain

Sets the signal level at terminal AM that is equal to 100% of the selected

monitor value.

Default: 50.0%

Min.: -999.9

Max.: 999.9

229

H4-06

(422)

Multi-Function Analog

Output Terminal AM Bias

Sets the signal level at terminal AM that is equal to 0% of the selected monitor

value.

Default: 0.0%

Min.: -999.9

Max.: 999.9

229

H4-07

(423)

Multi-Function Analog

Output Terminal FM Signal

Level Selection

0: 0 to 10 V

1: -10 to 10 V

2: 4 to 20mA

Default: 0

Range: 0 to 2

230

H4-08

(424)

Multi-Function Analog

Output Terminal AM Signal

Level Selection

0: 0 to 10 V

1: -10 to 10 V

2: 4 to 20 mA

Default: 0

Range: 0 to 2

230

B.7 H Parameters: Multi-Function Terminals

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

439