H2: Multi-Function Digital Outputs

No.

(Addr.

Hex)

Name

Description

Values

Page

H2-01

(40B)

Terminal M1-M2 function

selection (relay)

Refer to H2 Multi-Function Digital Output Settings on pages

436

to

437

for

descriptions of setting values.

Default: 0

Range: 0 to 192

214

H2-02

(40C)

Terminal M3-M4 function

selection (relay)

Default: 1

Range: 0 to 192

214

H2-03

(40D)

Terminal MD-ME-MF

Function Selection

Default: 2

Range: 0 to 192

214

H2-06

(437)

Watt Hour Output Unit

Selection

Outputs a 200 ms pulse signal when the watt-hour counter increases by the

units selected.

0: 0.1 kWh units

1: 1 kWh units

2: 10 kWh units

3: 100 kWh units

4: 1000 kWh units

Default: 0

Range: 0 to 4

223

H2 Multi-Function Digital Output Settings

H2-oo

Setting

Function

Description

Page

0

During run

Closed: A Run command is active or voltage is output.

215

1

Zero speed

Open: Output frequency is above the minimum output frequency set in E1-09.

Closed: Output frequency is below the minimum output frequency set in E1-09.

215

2

Speed agree 1

Closed: Output frequency equals the speed reference (plus or minus the hysteresis set to L4-02).

215

3

User-set speed agree 1

Closed: Output frequency and speed reference equal L4-01 (plus or minus the hysteresis set to

L4-02).

216

4

Frequency detection 1

Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis determined

by L4-02.

216

5

Frequency detection 2

Closed: Output frequency is greater than or equal to the value in L4-01 with hysteresis determined

by L4-02.

217

6

Drive ready

Closed: Power up is complete and the drive is ready to accept a Run command.

217

7

DC bus undervoltage

Closed: DC bus voltage is below the Uv trip level set in L2-05.

217

8

During baseblock (N.O.)

Closed: Drive has entered the baseblock state (no output voltage).

218

9

Frequency reference source

Open: External Reference 1 or 2 supplies the frequency reference (set in b1-01 or b1-15).

Closed: Digital operator supplies the frequency reference.

218

A

Run command source

Open: External Reference 1 or 2 supplies the Run command (set in b1-02 or b1-16).

Closed: Digital operator supplies the Run command.

218

B

Torque detection 1 (N.O.)

Closed: An overtorque or undertorque situation has been detected.

218

C

Frequency reference loss

Closed: Analog frequency reference has been lost.

Frequency reference loss is detected when the frequency reference drops below 10% of the

reference within 400 ms.

218

D

Braking resistor fault

Closed: Braking resistor or transistor is overheated or faulted out.

218

E

Fault

Closed: Fault occurred.

218

F

Through mode

Set this value when using the terminal in the pass-through mode.

218

10

Minor fault

Closed: An alarm has been triggered, or the IGBTs have reached 90% of their expected life span.

218

11

Fault reset command active

Closed: A command has been entered to clear a fault via the input terminals or from the serial

network.

218

12

Timer output

Closed: Timer output.

219

13

Speed agree 2

Closed: When drive output frequency equals the frequency reference ±L4-04.

219

14

User-set speed agree 2

Closed: When the drive output frequency is equal to the value in L4-03 ±L4-04.

219

15

Frequency detection 3

Closed: When the drive output frequency is less than or equal to the value in L4-03 ±L4-04.

220

16

Frequency detection 4

Closed: When the output frequency is greater than or equal to the value in L4-03 ±L4-04.

220

17

Torque detection 1 (N.C.)

Open: Overtorque or undertorque has been detected.

218

18

Torque detection 2 (N.O.)

Closed: Overtorque or undertorque has been detected.

19

Torque detection 2 (N.C.)

Open: Overtorque or undertorque has been detected.

218

1A

During reverse

Closed: Drive is running in the reverse direction.

220

1B

During baseblock (N.C.)

Open: Drive has entered the baseblock state (no output voltage).

221

B.7 H Parameters: Multi-Function Terminals

436

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual