Bias

Output

frequency

Bias value is increased using the
accel/decel times as set in d4-04

Up 2 command

Figure 5.33 Up/Down 2 Bias when d4-03 = 0.00 Hz

Setting d4-03 ≠ 0.00 Hz

When an Up 2 or Down 2 command is enabled, the bias is increased or decreased in steps for the value set in d4-03. The

frequency reference changes with the accel/decel times determined by parameter d4-04.

Bias

Output

frequency

Up 2 command

Bias value is increased in steps as
defined in d4-03
Drive uses accel/decel times as
set in d4-04

Figure 5.34 Up/Down 2 Bias when d4-03 > 0.00 Hz

n

d4-04: Frequency Reference Bias Accel/Decel (Up/Down 2)

Determines the accel/decel times used to increase or decrease the frequency reference or bias when using the Up/Down 2

function.

No.

Parameter Name

Setting Range

Default

d4-04

Frequency Reference Bias Accel/Decel (Up/Down 2)

0, 1

0

Setting 0: Current Accel/Decel Time

The drive uses the currently active accel/decel time.

Setting 1: Accel/Decel Time 4

The drive uses accel/decel time 4 set to parameters C1-07 and C1-08.

Note:

The functionality of setting 1 is only accessible via MEMOBUS/Modbus communications.

n

d4-05: Frequency Reference Bias Operation Mode Selection (Up/Down 2)

Determines if the bias value is held when the Up/Down 2 inputs are both released or both enabled. The parameter is effective

only when parameter d4-03 is set to 0.00.

No.

Parameter Name

Setting Range

Default

d4-05

Frequency Reference Bias Operation Mode Selection

(Up/Down 2)

0, 1

0

Setting 0: Hold Bias Value

The bias value will be held if no input Up 2 or Down 2 is active.

Setting 1: Reset Bias Value

The bias is reset to 0% when inputs Up 2 and Down 2 are both on or both off. The drive will use the accel/decel time as selected

in d4-04 to accelerate or decelerate to the frequency reference value.