beautypg.com

Enter command, Enter command types, Enter command settings when upgrading the drive – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 514: C.10 enter command, Communications, Refer, Refer to

background image

C.10 Enter Command

When writing parameters to the drive from the PLC using MEMOBUS/Modbus communication, parameter H5-11 determines

whether an Enter command must be issued to enable these parameters. This section describes the types and functions of the

Enter commands.

u

Enter Command Types

The drive supports two types of Enter commands as shown in

Table C.7

. An Enter command is enabled by writing 0 to register

numbers 0900H or 0910H. It is only possible to write to these registers; attempting to read from these registers will cause an

error.

Table C.7 Enter Command Types

Register No.

Description

0900H

Simultaneously writes data into the EEPROM (non-volatile memory) of the drive and enables the data in RAM. Parameter

changes remain after cycling power.

0910H

Writes data in the RAM only. Parameter changes are lost when the drive is shut off.

Note:

The EEPROM can only be written to 100,000 times, so it is recommended to limit the number of times writing to the EEPROM. The Enter

command registers are write-only and if these registers are read, the register address will be invalid (Error code: 02H). An Enter command

is not required when reference or broadcast data are sent to the drive.

u

Enter Command Settings when Upgrading the Drive

When replacing previous Yaskawa drive models with the P1000 and keeping the MEMOBUS/Modbus communications

settings, set parameter H5-11 in accordance with the Enter command configuration in the older drive. H5-11 determines

whether an Enter command is necessary to activate parameter changes in the drive.
• If upgrading from a G7, F7, or P7 series drive to a P1000, set parameter H5-11 to 0.
• If upgrading from a V7 series drive to a P1000, set parameter H5-11 to 1.

n

H5-11 and the Enter Command

An enter command is not required when writing registers 0000H to 001FH. Changes to those registers take effect immediately,

independent of the setting in parameter H5-11.

H5-11 Settings

H5-11 = 0

H5-11 = 1

Drive being replaced

G7, F7, P7

V7

How parameter settings are enabled When the Enter command is received from the master.

As soon as the value is changed.

Upper/lower limit check

Upper/lower limit check is performed, taking the settings

of related parameters into account.

Checks only the upper/lower limits of the parameters that

were changed.

Default value of related parameters Not affected. The settings of related parameters remain

unchanged. They must be changed manually if needed.

Default settings of related parameters are changed

automatically.

Error handling when setting

multiple parameters

Data is accepted even if one setting is invalid. The invalid

setting will be discarded. No error message occurs.

Error occurs if only one setting is invalid. All data that

was sent are discarded.

C.10 Enter Command

514

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

This manual is related to the following products: