Motor coasts

DC Injection Braking

with the current set in

b2-02

Run

command

Output

frequency

ON

OFF

Motor speed

Minimum Baseblock

Time (L2-03)

Figure 5.4 DC Injection Braking to Stop

DC Injection Braking time is determined by the value set to b2-04 and the output frequency at the time the Run command is

removed. It can be calculated by:

DC Injection brake time

(b2-04) x 10 x Output frequency

Max. output frequency (E1-04)

=

Output frequency when

Stop command was entered

100%

(Maximum output

frequency)

10%

DC Injection braking time

b2-04×10

b2-04

Figure 5.5 DC Injection Braking Time Depending on Output Frequency

Note:

If an overcurrent (oC) fault occurs during DC Injection Braking to Stop, lengthen the minimum baseblock time (L2-03) until the fault no

longer occurs.

Setting 3: Coast to Stop with Timer

When the Run command is removed, the drive will turn off its output and the motor will coast to stop. The drive will not start

if a Run command is input before the time t (C1-02) has expired. Cycle the Run command that was activated during time t

after t has expired to start the drive.

Drive output shut off

Run wait time t

Run command

Output

frequency

ON

ON

ON

OFF

OFF

Figure 5.6 Coast to Stop with Timer

The wait time t is determined by the output frequency when the Run command is removed and by the active deceleration time.