beautypg.com

U1 - 12, U1 - 19 – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 459

background image

No.

(Addr.

Hex)

Name

Description

Analog Output Level

Unit

U1-12

(4B)

Drive Status

Verifies the drive operation status.

U1 - 12=

00000000

During run
During zero-speed
During REV
During fault reset
signal input
During speed agree
Drive ready
During alarm
detection
During fault detection

1

1

1

1
1

1

1
1

No signal output

available

U1-13

(4E)

Terminal A1 Input Level Displays the signal level to analog input terminal A1.

10 V: 100%

0.1%

U1-14

(4F)

Terminal A2 Input Level Displays the signal level to analog input terminal A2.

10 V: 100%

0.1%

U1-15

(50)

Terminal A3 Input Level Displays the signal level to analog input terminal A3.

10 V: 100%

0.1%

U1-16

(53)

Output Frequency after

Soft Starter

Displays output frequency with ramp time and S-curves. Units determined

by o1-03.

10 V: Max frequency

0.01 Hz

U1-18

(61)

oPE Fault Parameter

Displays the parameter number that caused the oPE02 operation error.

No signal output

available

U1-19

(66)

MEMOBUS/Modbus

Error Code

Displays the contents of a MEMOBUS/Modbus error.

U1 - 19=

00000000

CRC Error
Data Length Error
Not Used

Parity Error
Overrun Error
Framing Error

Timed Out

Not Used

1

1

0

1

1

1

1

0

No signal output

available

U1-24

(7D)

Input Pulse Monitor

Displays the frequency to pulse train input terminal RP.

Determined by H6-02

1 Hz

U1-25

(4D)

Software Number (Flash) FLASH ID

No signal output

available

U1-26

(5B)

Software No. (ROM)

ROM ID

No signal output

available

U1-29

(7AA)

Software No. (PWM)

PWM ID

No signal output

available

U1-75

(851)

Time-Hour/Minute

Displays the current time (Hours and Minutes).

No signal output

available

U1-76

(852)

Date – Year

Displays the current year.

No signal output

available

U1-77

(853)

Date – Month/Day

Displays the current date (Month and Date).

No signal output

available

U1-78

(854)

Date – Week Day

Displays the current date of the week.

0: Sunday

1: Monday

2: Tuesday

3: Wednesday

4: Thursday

5: Friday

6: Saturday

No signal output

available

<1> The number of decimal places in the parameter value depends on the drive model and the ND selection. This value has two decimal places (0.01

A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if the maximum applicable
motor capacity is higher than 11 kW.

<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.

B.13 U: Monitors

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

459

B

Parameter List

This manual is related to the following products: