U1 - 12, U1 - 19 – Yaskawa AC Drive-P1000 Industrial Fan User Manual
Page 459

No.
(Addr.
Hex)
Name
Description
Analog Output Level
Unit
U1-12
(4B)
Drive Status
Verifies the drive operation status.
U1 - 12=
00000000
During run
During zero-speed
During REV
During fault reset
signal input
During speed agree
Drive ready
During alarm
detection
During fault detection
1
1
1
1
1
1
1
1
No signal output
available
–
U1-13
(4E)
Terminal A1 Input Level Displays the signal level to analog input terminal A1.
10 V: 100%
0.1%
U1-14
(4F)
Terminal A2 Input Level Displays the signal level to analog input terminal A2.
10 V: 100%
0.1%
U1-15
(50)
Terminal A3 Input Level Displays the signal level to analog input terminal A3.
10 V: 100%
0.1%
U1-16
(53)
Output Frequency after
Soft Starter
Displays output frequency with ramp time and S-curves. Units determined
by o1-03.
10 V: Max frequency
0.01 Hz
U1-18
(61)
oPE Fault Parameter
Displays the parameter number that caused the oPE02 operation error.
No signal output
available
–
U1-19
(66)
MEMOBUS/Modbus
Error Code
Displays the contents of a MEMOBUS/Modbus error.
U1 - 19=
00000000
CRC Error
Data Length Error
Not Used
Parity Error
Overrun Error
Framing Error
Timed Out
Not Used
1
1
0
1
1
1
1
0
No signal output
available
–
U1-24
(7D)
Input Pulse Monitor
Displays the frequency to pulse train input terminal RP.
Determined by H6-02
1 Hz
U1-25
(4D)
Software Number (Flash) FLASH ID
No signal output
available
–
U1-26
(5B)
Software No. (ROM)
ROM ID
No signal output
available
–
U1-29
(7AA)
Software No. (PWM)
PWM ID
No signal output
available
–
U1-75
(851)
Time-Hour/Minute
Displays the current time (Hours and Minutes).
No signal output
available
–
U1-76
(852)
Date – Year
Displays the current year.
No signal output
available
–
U1-77
(853)
Date – Month/Day
Displays the current date (Month and Date).
No signal output
available
–
U1-78
(854)
Date – Week Day
Displays the current date of the week.
0: Sunday
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
No signal output
available
–
<1> The number of decimal places in the parameter value depends on the drive model and the ND selection. This value has two decimal places (0.01
A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if the maximum applicable
motor capacity is higher than 11 kW.
<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.
B.13 U: Monitors
YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual
459
B
Parameter List