beautypg.com

B.15 defaults by drive model – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 468

background image

No.

Name

Unit

Default Settings

Model CIMR-Po

2A0040

2A0056

2A0069

2A0081

o2-04

Drive Model Selection

Hex.

6B

6D

6E

6F

E2-11

Motor Rated Power

kW

(HP)

11

(15)

15

(20)

18.5

(25)

22

(30)

b3-04

V/f Gain during Speed Search

%

100

100

100

100

b3-06

Output Current 1 during Speed Search

0.5

0.5

0.5

0.5

b3-07

Output Current 2 during Speed Search

(Speed Estimation Type)

b3-26

Start Speed Search Select

b8-03

Energy Saving Control Filter Time Constant

s

0.50

0.50

0.50

0.50

b8-04

Energy Saving Coefficient Value

70.44

63.13

57.87

51.79

C5-17

Motor Inertia

kgm

2

0.053

0.076

0.138

0.165

C6-02

Carrier Frequency Selection

7

7

7

7

E2-01

Motor Rated Current

A

39.7

53

65.8

77.2

E2-02

Motor Rated Slip

Hz

1.7

1.6

1.67

1.7

E2-03

Motor No-Load Current

A

11.2

15.2

15.7

18.5

E2-05

Motor Line-to-Line Resistance

Ω

0.23

0.138

0.101

0.079

E2-06

Motor Leakage Inductance

%

19.5

17.2

15.7

19.5

E2-10

Motor Iron Loss for Torque Compensation

W

245

272

505

538

L2-02

Momentary Power Loss Ride-Thru Time

s

1

2

2

2

L2-03

Momentary Power Loss Minimum Baseblock Time

s

0.9

1

1

1

L2-04

Momentary Power Loss Voltage Recovery Time

s

0.3

0.6

0.6

0.6

L3-24

Motor Acceleration Time for Inertia Calculations

s

0.265

0.244

0.317

0.355

L8-02

Overheat Alarm Level

°C

125

120

120

125

L8-35

Installation Method Selection

2

2

2

2

L8-38

Carrier Frequency Reduction Selection

2

2

2

2

n1-03

Hunting Prevention Time Constant

ms

10

10

10

10

B.15 Defaults by Drive Model

468

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

This manual is related to the following products: