beautypg.com

D.3 ul and csa standards – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 533

background image

Drive Model

Terminal

Recomm. Gauge

AWG, kcmil

Wire Range

AWG, kcmil

Screw

Size

Tightening Torque

N·m (lb.in.)

4A0362

R/L1, S/L2, T/L3

4/0 × 2P

3/0 to 600

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

4/0 × 2P

3/0 to 600

⊖, ⊕1

4/0 to 600

⊕3

3/0 to 600

M10

18 to 23

(159 to 204)

1

1 to 350

M12

32 to 40

(283 to 354)

4A0414

R/L1, S/L2, T/L3

300 × 2P

4/0 to 300

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

300 × 2P

4/0 to 300

⊖, ⊕1

3/0 to 300

⊕3

3/0 to 300

1

1 to 3/0

4A0515

R/L1, S/L2, T/L3

3/0 × 4P

3/0 to 300

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

4/0 × 4P

3/0 to 300

⊖, ⊕1

1/0 to 300

⊕3

1/0 to 300

1/0

1/0 to 300

4A0675

R/L1, S/L2, T/L3

300 × 4P

4/0 to 300

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

300 × 4P

4/0 to 300

⊖, ⊕1

1/0 to 300

⊕3

1/0 to 300

2/0

2/0 to 300

4A0930

R/L1, S/L2, T/L3, R1/L11, S1/L21,
T1/L31

4/0 × 4P×2

3/0 to 300

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

4/0 × 4P×2

3/0 to 300

⊖, ⊕1

4/0 to 300

⊕3

4/0 to 300

3/0

3/0 to 250

4A1200

R/L1, S/L2, T/L3, R1/L11, S1/L21,
T1/L31

300 × 4P×2

4/0 to 300

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

300 × 4P×2

4/0 to 300

⊖, ⊕1

250 to 300

⊕3

4/0 to 300

4/0

4/0 to 250

<1> Install a GFCI when using this wire gauge in accordance with IEC/EN 61800-5-1.
<2> Install a GFCI or use 10 mm

2

(AWG 8) copper wire when using this wire gauge in accordance with IEC/EN 61800-5-1.

D.3 UL and CSA Standards

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

533

D

Standards Compliance

This manual is related to the following products: