5 e: motor parameters, Setting a custom v/f pattern (setting f: default) – Yaskawa AC Drive-P1000 Industrial Fan User Manual
Page 193

Table 5.25 Rated Torque Characteristics, Settings 0 to 3
Setting = 0
50 Hz
Setting = 1
60 Hz
Setting = 2
60 Hz
Setting = 3
72 Hz
0
6
200
1.3 2.5
50
12
V
oltage (V)
Frequency (Hz)
0
6
200
1.5 3
60
12
V
oltage (V)
Frequency (Hz)
0
6
12
200
1.5 3
60
50
V
oltage (V)
Frequency (Hz)
0
6
12
200
1.5 3
72
60
V
oltage (V)
Frequency (Hz)
Table 5.26 Derated Torque Characteristics, Settings 4 to 7
Setting = 4
50 Hz
Setting = 5
50 Hz
Setting = 6
60 Hz
Setting = 7
60 Hz
0
5
200
1.3
25
50
35
V
oltage (V)
Frequency (Hz)
0
6
200
1.3
25
50
50
V
oltage (V)
Frequency (Hz)
0
5
200
1.5
30
60
35
V
oltage (V)
Frequency (Hz)
0
6
200
1.5
30
60
50
V
oltage (V)
Frequency (Hz)
Table 5.27 High Starting Torque, Settings 8 to B
Setting = 8
50 Hz
Setting = 9
50 Hz
Setting = A
60 Hz
Setting = B
60 Hz
0
7
200
1.3 2.5
50
15
V
oltage (V)
Frequency (Hz)
0
9
200
1.3 2.5
50
20
V
oltage (V)
Frequency (Hz)
0
7
200
1.5 3
60
15
V
oltage (V)
Frequency (Hz)
0
11
200
1.5 3
60
20
V
oltage (V)
Frequency (Hz)
Table 5.28 Constant Output, Settings C to F
Setting = C
90 Hz
Setting = D
120 Hz
Setting = E
180 Hz
Setting = F
60 Hz
0
6
12
200
1.5 3
90
60
V
oltage (V)
Frequency (Hz)
0
6
12
200
1.5 3
120
60
V
oltage (V)
Frequency (Hz)
0
6
12
200
1.5 3
180
60
V
oltage (V)
Frequency (Hz)
0
6.9
230
1.5 3
60
13.8
V
oltage (V)
Frequency (Hz)
Setting a Custom V/f Pattern (Setting F: Default)
Setting parameter E1-03 to F allows the user to set up a custom V/f pattern by changing parameters E1-04 to E1-13.
When initialized, the default values for parameters E1-04 to E1-13 will be equal to Predefined V/f pattern 1.
n
V/f Pattern Settings E1-04 to E1-13
If E1-03 is set to a preset V/f pattern (i.e., a value other than F), the user can monitor the V/f pattern in parameters E1-04
through E1-13. To create a new V/f pattern, set E1-03 to F.
Refer to V/f Pattern on page 194
pattern.
No.
Parameter Name
Setting Range
Default
E1-04
Maximum Output Frequency
40.0 to 400.0 Hz
60.0 Hz
E1-05
Maximum Voltage
0.0 to 255.0 V
<4>
575.0 V
E1-06
Base Frequency
0.0 to [E1-04]
60.0 Hz
E1-07
Middle Output Frequency
0.0 to [E1-04]
3.0 Hz
E1-08
Middle Output Frequency Voltage
0.0 to 255.0 V
<4>
15.0 V
E1-09
Minimum Output Frequency
0.0 to [E1-04]
1.5 Hz
E1-10
Minimum Output Frequency Voltage
0.0 to 255.0 V
<4>
9.0 V
5.5 E: Motor Parameters
YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual
193
5
Parameter Details