No.

Name

Setting Range

Default

o1-10

User-Set Display Units Maximum Value

1 to 60000

Determined by

o1-03

n

o1-11: User-Set Display Units Decimal Display

Determines how many decimal points should be used to set and display the frequency reference.

No.

Name

Setting Range

Default

o1-11

User-Set Display Units Decimal Display

0 to 3

Determined by

o1-03

Setting 0: No Decimal Point
Setting 1: One Decimal Point
Setting 2: Two Decimal Points
Setting 3: Three Decimal Points

n

o1-13: Frequency Reference and Frequency Related Monitor Custom Units 1

Sets the first character of the customer-specified unit display when o1-03 is set to 3 and o1-09 is set to 24.

No.

Name

Setting Range

Default

o1-13

Frequency Reference and Frequency Related Monitor Custom Units

1

30 to 7A

41

n

o1-14: Frequency Reference and Frequency Related Monitor Custom Units 2

Sets the second character of the customer-specified unit display when o1-03 is set to 3 and o1-09 is set to 24.

No.

Name

Setting Range

Default

o1-14

Frequency Reference and Frequency Related Monitor Custom Units

2

30 to 7A

41

n

o1-15: Frequency Reference and Frequency Related Monitor Custom Units 3

Sets the third character of the customer-specified unit display when o1-03 is set to 3 and o1-09 is set to 24.

No.

Name

Setting Range

Default

o1-14

Frequency Reference and Frequency Related Monitor Custom Units

3

30 to 7A

41

u

o2: Digital Operator Keypad Functions

These parameters determine the functions assigned to the operator keys.

n

o2-01: LO/RE (LOCAL/REMOTE) Key Function Selection

Determines whether the LO/RE key on the digital operator will be enabled for switching between LOCAL and REMOTE.

No.

Name

Setting Range

Default

o2-01

LO/RE Key Function Selection

0, 1

1

Setting 0: Disabled

The LO/RE key is disabled.

Setting 1: Enabled

The LO/RE switches between LOCAL and REMOTE operation. Switching is possible during stop only. When LOCAL is

selected, the LED indicator on the LO/RE key will light up.

WARNING!

Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching from

LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Check all mechanical or electrical connections

thoroughly before making any setting changes to o2-01 and b1-07.

Table 5.36

lists the setting combinations for o2-01 and b1-07.

5.10 o: Operator Related Settings

268