beautypg.com

Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 350

background image

n

Installing the Cooling Fan

NOTICE:

Prevent Equipment Damage. Follow cooling fan replacement instructions. Improper cooling fan replacement could result in

damage to equipment. When installing the replacement cooling fan into the drive, make sure the fan is facing upwards. To ensure maximum

useful product life, replace all cooling fans when performing maintenance.

Reverse the procedure described above to reinstall the cooling fan.

1.

Install the replacement cooling fan into the drive, ensuring the alignment pins line up as shown in the figure below.

A

B

C

A – Push the connectors together so no

space remains between them

B – Label facing up

C – Make sure the alignment pins line up

properly

Figure 7.5 Install the Cooling Fan: 2A0018 to 2A0081, 4A0007 to 4A0044, and 5A0006 to 5A0032

2.

Properly connect the fan power lines, then place the cable back into the recess of the drive.

A

B

A – Back

B – Front

Figure 7.6 Connect the Cooling Fan Power Supply Connectors: 2A0018 to 2A0081, 4A0007 to 4A0044,

and 5A0006 to 5A0032

3.

While pressing in on the hooks on the left and right sides of the fan finger guard, guide the fan finger guard until it

clicks back into place.

Figure 7.7 Reattach the Fan Finger Guard: 2A0018 to 2A0081, 4A0007 to 4A0044, and 5A0006 to 5A0032

4.

Turn on the power supply and set o4-03 to 0 to reset the Maintenance Monitor cooling fan operation time.

7.4 Drive Cooling Fans

350

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

This manual is related to the following products: