Setting 2: Drive dedicated motor (speed range for constant torque: 1:10)

Use this setting when operating a drive duty motor that allows constant torque in a speed range of 1:10. The drive will allow

the motor to run with 100% load from 10% up to 100% speed. Running at slower speeds with full load can trigger an overload

fault.

Overload Tolerance

Cooling Ability

Overload Characteristics

A: Max. speed for 200LJ and above
B: Max. speed for 160MJ to 180 LJ
C: Max. speed for 132MJ and below

Rated Speed=100% Speed

60 s

Continuous

A

B

C

Speed (%)

Torque (%)

100

150

110

100120 167 200

55

50

0

Motor is designed to effectively cool

itself even at low speeds.

Continuous operation with 100% load

from 6 Hz to E1-06, Motor Base

Frequency.

Setting 3: Vector motor (speed range for constant torque: 1:100)

Use this setting when operating a drive-dedicated motor that allows constant torque in a speed range of 1:100. This motor type

is allowed to run with 100% load from 1% up to 100% speed. Running slower speeds with full load can trigger an overload

fault.

Overload Tolerance

Cooling Ability

Overload Characteristics

A: Max. speed for 200LJ and above
B: Max. speed for 160MJ to 180 LJ
C: Max. speed for 132MJ and below

150

100

90

50

0 1

100120 167 200

A

B

C

Continuous

Speed (%)

Rated Speed=100% Speed

Torque (%)

60 s

Motor is designed to effectively cool

itself at speeds near 0.6 Hz.

Continuous operation with 100% load

from 0.6 Hz to E1-06, Motor Base

Frequency.

Continuous operation below 0.6 Hz

may cause an oL1 or oL2 fault.

Setting 6: General-purpose Motor

Note:

General-purpose motors are designed with a base speed that operates at line frequency (50/60 Hz depending on geographic region).

Because the motor is self-cooled, the overload tolerance drops when the motor speed is lowered. The drive appropriately

adjusts the electrothermal trigger point according to the motor overload characteristics and protects the motor from overheat

throughout the entire speed range.

Overload Tolerance

Cooling Ability

Overload Characteristics

A: Max. speed for 200LJ and above
B: Max. speed for 160MJ to 180 LJ
C: Max. speed for 132MJ and below

05 33 100 120 167 200

Speed (%)

Continuous

A

B

C

Rated Speed=100% Speed

60 s

150

100

90

60

50

Torque (%)

Motor designed to operate from line

power. Motor cooling is most effective

when running at rated base frequency

(check the motor nameplate or

specifications)

Continuous operation at less than line

power frequency with 100% load can

trigger motor overload protection

(oL1). A fault is output and the motor

will coast to stop.

5.8 L: Protection Functions

234

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual