Setting 1: 0.01% (100.00%: Maximum Frequency)

The setpoint and PID monitors are displayed as a percentage with a resolution of 0.01%.

Setting 2: r/min (Set the Motor Poles)

The setpoint and PID monitors are displayed in r/min with a resolution of 1 r/min.

Setting 3: User Defined (Determined by b5-38 and b5-39)

Parameters b5-38 and b5-39 determine the units based on b5-46 setting.

n

b5-38, b5-39: PID Setpoint User Display, PID Setpoint Display Digits

When parameter b5-20 is set to 3, parameters b5-38 and b5-39 set a user-defined display for the PID setpoint (b5-19) and PID

feedback monitors (U5-01, U5-04).
Parameter b5-38 determines the display value when the maximum frequency is output and parameter b5-39 determines the

number of digits. The setting value is equal to the number of decimal places.

No.

Name

Setting Range

Default

b5-38

PID Setpoint User Display

1 to 60000

10000

b5-39

PID Setpoint Display Digits

0 to 3

2

Setting 0: No decimal places
Setting 1: One decimal place
Setting 2: Two decimal places
Setting 3: Three decimal places

n

b5-46: PID Setpoint Monitor Unit Selection

Sets the digital operator display units in U5-01 and U5-04 when b5-20 is set to 3.

No.

Name

Setting Range

Default

b5-46

PI Setpoint Monitor Unit Selection

0 to 15; 25

0

Setting 0: WC (Inch of Water)
Setting 1: PSI (Pounds per Square Inch)
Setting 2: GPM (Gallons per Minute)
Setting 3: F (Degrees Fahrenheit)
Setting 4: CFM (Cubic Feet per Minute)
Setting 5: CMH (Cubic Meters per Hour)
Setting 6: LPH (Liters per Hour)
Setting 7: LPS (Liters per Second)
Setting 8: Bar (Bar)
Setting 9: Pa (Pascal)
Setting 10: C (Degrees Celsius)
Setting 11: Mtr (Meters)
Setting 12: Ft (Feet)
Setting 13: LPN (Liters per Minute)
Setting 14: CMM (Cubic Meters per Minute)
Setting 15: “Hg (Inches of Mercury)
Setting 25: None

n

b5-89: Sleep Method Selection

Determines how the drive sleeps and wakes-up when using PID.

No.

Name

Setting Range

Default

b5-89

Sleep Method Selection

0, 1

0

5.2 b: Application

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

169

5

Parameter Details