beautypg.com

H4: multi-function analog outputs – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 229

background image

Setting E: Motor Temperature

In addition to motor overload fault detection oL1, it is possible to use a Positive Temperature Coefficient (PTC) thermistor

for motor insulation protection.

Refer to Motor Protection Using a Positive Temperature Coefficient (PTC) Thermistor on

page 235

for a detailed explanation.

Setting 16: Differential PID Feedback

If an analog value is set for this function, the PID controller is set for differential feedback. The difference of the PID feedback

input value and the differential feedback input value builds the feedback value used to calculate the PID input.

Refer to PID

Feedback Input Methods on page 160

.

Setting 17: Motor Thermistor (NTC)

Used as a complement or a substitution for oL1.

Refer to Motor Protection Using an NTC Thermistor Input on page 237

for details.

Setting 1F: Through Mode

An input does not affect any drive function, but the input level can still be read out by a PLC via a communication option or

MEMOBUS/Modbus communications.

Setting 25: Secondary PI Setpoint

10 V = S3-02 (maximum output frequency)

Setting 26: Secondary PI Feedback

10 V = S3-02 (maximum output frequency)

u

H4: Multi-Function Analog Outputs

These parameters assign functions to analog output terminals FM and AM for monitoring a specific aspect of drive

performance.

n

H4-01, H4-04: Multi-Function Analog Output Terminal FM, AM Monitor Selection

Sets the desired drive monitor parameter Uo-oo to output as an analog value via terminal FM and AM.

Refer to U: Monitor

Parameters on page 285

for a list of all monitors. The “Analog Output Level” column indicates whether a monitor can be

used for analog output.
Example: Enter “103” for U1-03.

No.

Name

Setting Range

Default

H4-01

Multi-Function Analog Output Terminal FM Monitor Selection

000 to 999

102

H4-04

Multi-Function Analog Output Terminal AM Monitor Selection

000 to 999

103

A setting of 031 or 000 applies no drive monitor to the analog output. With either of these settings, the output level of the

terminals FM and AM can be set by a PLC via a communication option or MEMOBUS/Modbus (through mode).

n

H4-02, H4-03: Multi-Function Analog Output Terminal FM Gain and Bias

H4-05, H4-06: Multi-Function Analog Output Terminal AM Gain and Bias

Parameters H4-02 and H4-05 set the terminal FM and AM output signal level when the value of the selected monitor is at

100%. Parameters H4-03 and H4-06 set the terminal FM and AM output signal level when the value of the selected monitor

is at 0%. Both are set as a percentage, where 100% equals 10 Vdc or 20 mA analog output and 0% equals 0 V or 4 mA. The

output voltage of both terminals is limited to +/-10 Vdc.
The output signal range can be selected between 0 to +10 Vdc or -10 to +10 Vdc, or 4 to 20 mA using parameter H4-07 and

H4-08.

Figure 5.63

illustrates how gain and bias settings work.

No.

Name

Setting Range

Default

H4-02

Multi-Function Analog Output Terminal FM Gain

-999.9 to 999.9%

100.0%

H4-03

Multi-Function Analog Output Terminal FM Bias

-999.9 to 999.9%

0.0%

H4-05

Multi-Function Analog Output Terminal AM Gain

-999.9 to 999.9%

50.0%

H4-06

Multi-Function Analog Output Terminal AM Bias

-999.9 to 999.9%

0.0%

Using Gain and Bias to Adjust Output Signal Level

The output signal is adjustable while the drive is stopped.

5.7 H: Terminal Functions

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

229

5

Parameter Details

This manual is related to the following products: