Command, Motor does not rotate – Yaskawa AC Drive-P1000 Industrial Fan User Manual
Page 329
Cause
Possible Solutions
The wrong password was entered.
• If the password entered to A1-04 does not match the password saved to A1-05, then drive
settings cannot be changed.
• Reset the password.
If you cannot remember the password:
•
Scroll to A1-04. Press
STOP
and
simultaneously. Parameter A1-05 will appear.
• Set a new password to parameter A1-05.
Undervoltage was detected.
• Check the drive input power voltage by looking at the DC bus voltage (U1-07).
• Check all main circuit wiring.
u
Motor Does Not Rotate Properly after Pressing RUN Button or after Entering External Run
Command
n
Motor Does Not Rotate
Cause
Possible Solutions
The drive is not in the Drive Mode.
• Check if the DRV light on the digital operator is lit.
• Enter the Drive Mode to begin operating the motor.
Refer to The Drive, Programming, and
Clock Adjustment Modes on page 114
was pushed.
Stop the drive and check if the correct frequency reference source is selected. If the operator keypad
shall be the source, the LO/RE button LED must be on. If the source is REMOTE, it must be off.
Take the following steps to solve the problem:
•
Push
.
• If o2-01 is set to 0, then the LO/RE button will be disabled.
Auto-Tuning has just completed.
• When Auto-Tuning completes, the drive is switched back to the Programming Mode. The Run
command will not be accepted unless the drive is in the Drive Mode.
• Use the digital operator to enter the Drive Mode.
Refer to The Drive, Programming, and Clock
A Fast Stop was executed and has not yet been reset. Reset the Fast Stop command.
Settings are incorrect for the source that provides the
Run command.
Check parameter b1-02 (Run Command Selection).
Set b1-02 so that it corresponds with the correct Run command source.
0: Digital operator
1: Control circuit terminal (default setting)
2: MEMOBUS/Modbus communications
3: Option card
There is faulty wiring in the control circuit terminals.
• Check the wiring for the control terminal.
• Correct wiring mistakes.
• Check the input terminal status monitor (U1-10).
The drive has been set to accept the frequency
reference from the incorrect source.
Check parameter b1-01 (Frequency Reference Selection 1).
Set b1-01 to the correct source of the frequency reference.
0: Digital operator
1: Control circuit terminal (default setting)
2: MEMOBUS/Modbus communications
3: Option card
4: Pulse train input (RP)
The terminal set to accept the main speed reference is
set to the incorrect voltage and/or current.
Refer to Terminals A1, A2, and A3 Input Signal Selection on page 100
Selection for the sink/source mode and the internal/
external power supply is incorrect.
Check jumper S3.
Refer to Sinking/Sourcing Mode for Digital Inputs on page 100
.
Frequency reference is too low.
• Check the frequency reference monitor (U1-01).
• Increase the frequency by changing the maximum output frequency (E1-09).
Multi-function analog input is set up to accept gain for
the frequency reference, but no voltage (current) has
been provided.
• Check the multi-function analog input settings.
• Check if analog input A1, A2, or A3 is set for frequency reference gain (H3-02, H3-10, H3-06
= 1). If so, check if the correct signal is applied to the terminal. The gain and the frequency
reference will be 0 if no signal is applied to the gain input.
• Check if H3-02, H3-10, and H3-06 have been set to the proper values.
• Check if the analog input value has been set properly. (U1-13 to U1-15)
6.10 Troubleshooting without Fault Display
YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual
329
6
Troubleshooting