B8: energy saving – Yaskawa AC Drive-P1000 Industrial Fan User Manual
Page 174

b6-01
b6-03
b6-02
b6-04
Run Command
Output Frequency
ON
OFF
OFF
Figure 5.21 Dwell Function at Start and Stop
n
b6-01, b6-02: Dwell Reference, Dwell Time at Start
Parameter b6-01 determines the frequency that is held for the time set in b6-02 during acceleration.
No.
Name
Setting Range
Default
b6-01
Dwell Reference at Start
0.0 to 400.0 Hz
0.0 Hz
b6-02
Dwell Time at Start
0.0 to 10.0 s
0.0 s
n
b6-03, b6-04: Dwell Reference, Dwell Time at Stop
Parameter b6-03 determines the frequency that is held for the time set in b6-04 during deceleration.
No.
Name
Setting Range
Default
b6-03
Dwell Reference at Stop
0.0 to 400.0 Hz
0.0 Hz
b6-04
Dwell Time at Stop
0.0 to 10.0 s
0.0 s
u
b8: Energy Saving
The Energy Saving feature improves overall system operating efficiency by operating the motor at its most efficient level.
Note:
1. Energy Saving is not designed for applications that experience instantaneous heavy loads or applications that rarely operate with light
load conditions.
2. Energy Saving is designed for applications with variable torque (Normal Duty) and is not appropriate for applications where the load
may suddenly increase.
3. The performance of the Energy Saving function depends on the accuracy of the motor data. Always perform Auto-Tuning and correctly
enter the motor data before using this function.
n
b8-01: Energy Saving Control Selection
Enables or disables the Energy Saving function.
No.
Parameter Name
Setting Range
Default
b8-01
Energy Saving Control Selection
0, 1
0
Setting 0: Disabled
Setting 1: Enabled
n
b8-04: Energy Saving Coefficient Value
Determines the level of maximum motor efficiency. Setting range is 0.0 to 2000.0 for drives 3.7 kW and smaller. The display
resolution depends on the rated output power of the drive.
No.
Name
Setting Range
Default
b8-04
Energy Saving Coefficient Value
0.00 to 655.00
Determined by
E2-11, and o2-04
Note:
The default value changes if the motor rated capacity set to E2-11 is changed. The Energy Saving coefficient is set automatically when
Auto-Tuning for Energy Saving is performed (
Refer to Auto-Tuning on page 129
).
n
b8-05: Power Detection Filter Time
Determines how often in milliseconds the output power is measured. The Energy Saving function continuously searches out
the lowest output voltage to achieve minimum output power.
5.2 b: Application
174
YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual