n

b6-01, b6-02: Dwell Reference, Dwell Time at Start

Parameter b6-01 determines the frequency that is held for the time set in b6-02 during acceleration.

No.

Name

Setting Range

Default

b6-01

Dwell Reference at Start

0.0 to 400.0 Hz

0.0 Hz

b6-02

Dwell Time at Start

0.0 to 10.0 s

0.0 s

n

b6-03, b6-04: Dwell Reference, Dwell Time at Stop

Parameter b6-03 determines the frequency that is held for the time set in b6-04 during deceleration.

No.

Name

Setting Range

Default

b6-03

Dwell Reference at Stop

0.0 to 400.0 Hz

0.0 Hz

b6-04

Dwell Time at Stop

0.0 to 10.0 s

0.0 s

u

b8: Energy Saving

The Energy Saving feature improves overall system operating efficiency by operating the motor at its most efficient level.

Note:

1. Energy Saving is not designed for applications that experience instantaneous heavy loads or applications that rarely operate with light

load conditions.

2. Energy Saving is designed for applications with variable torque (Normal Duty) and is not appropriate for applications where the load

may suddenly increase.

3. The performance of the Energy Saving function depends on the accuracy of the motor data. Always perform Auto-Tuning and correctly

enter the motor data before using this function.

n

b8-01: Energy Saving Control Selection

Enables or disables the Energy Saving function.

No.

Parameter Name

Setting Range

Default

b8-01

Energy Saving Control Selection

0, 1

0

Setting 0: Disabled

Setting 1: Enabled

n

b8-04: Energy Saving Coefficient Value

Determines the level of maximum motor efficiency. Setting range is 0.0 to 2000.0 for drives 3.7 kW and smaller. The display

resolution depends on the rated output power of the drive.

No.

Name

Setting Range

Default

b8-04

Energy Saving Coefficient Value

0.00 to 655.00

Determined by

E2-11, and o2-04

Note:

The default value changes if the motor rated capacity set to E2-11 is changed. The Energy Saving coefficient is set automatically when

Auto-Tuning for Energy Saving is performed (

Refer to Auto-Tuning on page 129

).

n

b8-05: Power Detection Filter Time

Determines how often in milliseconds the output power is measured. The Energy Saving function continuously searches out

the lowest output voltage to achieve minimum output power.

5.2 b: Application

174

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual