L4: Speed Detection

These parameters set up the speed agree and speed detection functions that can be assigned to the multi-function output

terminals.

n

L4-01, L4-02: Speed Agreement Detection Level and Detection Width

Parameter L4-01 sets the detection level for the digital output functions Speed agree 1, User-set speed agree 1, Frequency

detection 1, and Frequency detection 2.
Parameter L4-02 sets the hysteresis level for these functions.

No.

Name

Setting Range

Default

L4-01

Speed Agreement Detection Level

0.0 to 400.0 Hz

0.0 Hz

L4-02

Speed Agreement Detection Width

0.0 to 20.0 Hz

2.0 Hz

Refer to H2-01 to H2-03: Terminal M1-M2, M3-M4, and MD-ME-MF Function Selection on page 214

, Settings 2, 3, 4,

and 5.

n

L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-)

Parameter L4-03 sets the detection level for the digital output functions Speed agree 2, User-set speed agree 2, Frequency

detection 3, and Frequency detection 4.
Parameter L4-04 sets the hysteresis level for these functions.

No.

Name

Setting Range

Default

L4-03

Speed Agreement Detection Level (+/-)

-400.0 to 400.0 Hz

0.0 Hz

L4-04

Speed Agreement Detection Width (+/-)

0.0 to 20.0 Hz

2.0 Hz

Refer to H2-01 to H2-03: Terminal M1-M2, M3-M4, and MD-ME-MF Function Selection on page 214

, Settings 13, 14,

15, and 16.

n

L4-05: Frequency Reference Loss Detection Selection

The drive can detect a loss of an analog frequency reference from input A1, A2, or A3. Frequency reference loss is detected

when the frequency reference drops below 10% of the reference or below 5% of the maximum output frequency within 400

ms.

100%

400 ms

Analog

frequency

reference

Loss of

Reference

output

time

10%

ON

OFF

Figure 5.80 Loss of Reference Function

Set H2-01, H2-02, or H2-03 to C for a digital output to trigger when frequency reference loss occurs.

Refer to Setting C:

Frequency Reference Loss on page 218

for details on setting the output function.

Parameter L4-05 selects the operation when a frequency reference loss is detected.

No.

Name

Setting Range

Default

L4-05

Frequency Reference Loss Detection Selection

0, 1

0

Setting 0: Stop

Drive follows the frequency reference (which is no longer present) and stops the motor.

Setting 1: Continue operation with reduced frequency reference

The drive will continue operation at the frequency reference value set to parameter L4-06. When the external frequency

reference value is restored, the operation is continued with the frequency reference.

5.8 L: Protection Functions

252

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual