B.11 S: Special Application

u

S1: Dynamic Noise Control Function

No.

(Addr.

Hex)

Name

Description

Values

Page

S1-01

(3200)

Dynamic Audible Noise

Control Function Selection

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

274

S1-02

(3201)

Voltage Reduction Rate

Sets the rate at which the output voltage will be reduced as a percentage of the

V/f pattern when operating with no load.

Default: 50.0%

Min.: 50.0

Max.: 100.0

274

S1-03

(3202)

Voltage Restoration Level

Sets the level when the drive should start restoring the voltage as a percentage

of the drive rated torque.

Default: 20.0%

Min.: 0.0

Max.: 90.0

274

S1-04

(3203)

Voltage Restoration

Complete Level

Sets the level at which voltage restoration for the V/f pattern is complete as a

percentage of the drive rated torque. If the output torque rises above the value

of S1-04, then the voltage will be controlled in a manner specified by the V/f

pattern setting.

Default: 50.0%

Min.: S1-03 + 10.0

Max.: 100.0

275

S1-05

(3204)

Voltage Restoration

Sensitivity Time Constant

Sets the level of sensitivity of the output torque and LPF time constants for

the voltage reduction rate. The level of sensitivity can be adjusted in

accordance with the load response.

Default: 1.000 s

Min.: 0.000

Max.: 3.000

275

S1-06

(3205)

Voltage Restoration Time

Constant at Impact

Sets the voltage restoration time constant if an impact load is added.

Default: 0.050 s

Min.: 0.000

Max.: 1.000

275

S1-07

(323C)

Output Phase Loss Level for

Dynamic Noise Control

Reduces the output phase loss level when Dynamic Noise Control is active. Default: 100.0%

Min.: 10.0

Max.: 100.0

275

u

S2: Programmable Run Timers

No.

(Addr.

Hex)

Name

Description

Values

Page

S2-01

(3206)

Sequence Timer 1 Start

Time

Sets the start time for timer 1. The value must be set less than or equal to S2-02. Default: 00:00

Min.: 00:00
Max.: 24:00

<1>

278

S2-02

(3207)

Sequence Timer 1 Stop Time

Sets the stop time for timer 1. The value must be set greater than or equal to

S2-01.

Default: 00:00

Min.: 00:00
Max.: 24:00

<1>

279

S2-03

(3208)

Sequence Timer 1 Day

Selection

Sets the days for which sequence timer 1 is active.

0: Timer disabled

1: Daily

2: Mon - Fri

3: Sat - Sun

4: Monday

5: Tuesday

6: Wednesday

7: Thursday

8: Friday

9: Saturday

10: Sunday

10: Sunday

Default: 0

Range: 0 to 10

279

S2-04

(3209)

Sequence Timer 1 Selection

Sets the action that occurs when sequence timers 1 is active.

0: Digital output only

1: Run

2: Run - PI disable

Default: 0

Range: 0 to 2

279

S2-05

(320A)

Sequence Timer 1 Reference

Source

Selects the frequency reference source used for running the drive when

sequence timer 1 is active (only applicable when S2-04 is set to 1 or 2).

0: Operator (d1-01)

1: Operator (d1-02)

2: Operator (d1-03)

3: Operator (d1-04)

4: Terminals

5: Serial communication

6: Option card

7: Pulse input

Default: 0

Range: 0 to 7

279

B.11 S: Special Application

452