B.15 defaults by drive model – Yaskawa AC Drive-P1000 Industrial Fan User Manual
Page 470

No.
Name
Unit
Default Settings
–
Model CIMR-Po
–
2A0250
2A0312
2A0360
2A0415
o2-04
Drive Model Selection
Hex.
75
76
77
78
E2-11
Motor Rated Power
kW (HP)
30
(100)
37
(125)
45
(150)
55
(175)
b3-04
V/f Gain during Speed Search
%
80
80
80
80
b3-06
Output Current 1 during Speed Search
–
0.7
0.7
0.7
0.7
b3-07
Output Current 2 during Speed Search
(Speed Estimation Type)
–
–
–
–
–
b3-26
Start Speed Search Select
–
–
–
–
–
b8-03
Energy Saving Control Filter Time Constant
s
2.00
2.00
2.00
2.00
b8-04
Energy Saving Coefficient Value
–
23.1
20.65
18.12
18.12
C5-17
Motor Inertia
kgm
2
0.90
1.10
1.90
1.90
C6-02
Carrier Frequency Selection
–
7
7
7
7
E2-01
Motor Rated Current
A
260
260
260
260
E2-02
Motor Rated Slip
Hz
1.39
1.39
1.39
1.39
E2-03
Motor No-Load Current
A
72
72
72
72
E2-05
Motor Line-to-Line Resistance
Ω
0.023
0.023
0.023
0.023
E2-06
Motor Leakage Inductance
%
20
20
20
20
E2-10
Motor Iron Loss for Torque Compensation
W
1200
1200
1200
1200
L2-02
Momentary Power Loss Ride-Thru Time
s
2
2
2
2
L2-03
Momentary Power Loss Minimum Baseblock Time
s
1.5
1.5
1.7
1.7
L2-04
Momentary Power Loss Voltage Recovery Ramp Time
s
1
1
1
1
L3-24
Motor Acceleration Time for Inertia Calculations
s
0.533
0.592
0.646
0.646
L8-02
Overheat Alarm Level
°C
115
120
120
120
L8-35
Installation Method Selection
–
0
0
0
0
L8-38
Carrier Frequency Reduction Selection
–
2
2
2
2
n1-03
Hunting Prevention Time Constant
ms
10
10
100
100
B.15 Defaults by Drive Model
470
YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual