Changing parameter settings or valu, Changing parameter settings or values, Programming mode details – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 118: Press to enter the parameter menu tree, Press or to select the c parameter group, Press two times

background image

Figure 4.7

illustrates how to change the frequency reference from F 0.00 (0 Hz) to F 6.00 (6 Hz) while in the Drive Mode.

This example assumes the drive is set to LOCAL.

ESC

F1

F2

Frequency reference

display at power up

Press to select LOCAL

Press until the frequency

reference changes to 006.00 Hz

left

right

- MODE -

U1-01= 0.00Hz
U1-02= 0.00Hz

U1-03= 0.00A

DRV

FREF (OPR)

Rdy

JOG

FWD

FWD/REV

LSEQ

LREF

- MODE -

U1-01= 6.00Hz
U1-02= 0.00Hz

U1-03= 0.00A

DRV

FREF (OPR)

Rdy

JOG

FWD

FWD/REV

LSEQ

LREF

-MONITR-

FREF (d1-01)

U1-01=

0

00.00Hz

“0.00Hz”

DRV

FWD

Rdy

-MONITR-

FREF (d1-01)

U1-01= 00

6

.00Hz

“0.00Hz”

DRV

FWD

Rdy

-MONITR-

FREF (d1-01)

U1-01= 00

6

.00Hz

(0.00 ~ 60.00)

“0.00Hz”

DRV

FWD

Rdy

Entry Accepted

(0.00 ~ 60.00)

(0.00 ~ 60.00)

Figure 4.7 Setting the Frequency Reference while in the Drive Mode

Note:

The drive will not accept a change to the frequency reference until the ENTER key is pressed after the frequency reference is entered. This

feature prevents accidental setting of the frequency reference. To have the drive accept changes to the frequency reference as soon as changes

are made without requiring the ENTER key, set o2-05 to 1.

n

Programming Mode Details

The following actions are possible in the Programming Mode:
Parameter Setting Mode: Access and edit all parameter settings.
Verify Menu: View a list of parameters that have been changed from the default values.
Setup Group: Access a list of commonly used parameters to simplify setup (

Refer to Simplified Setup Using the Setup

Groups on page 121

).

Auto-Tuning Mode: Automatically calculate and set motor parameters to optimize drive performance.

u

Changing Parameter Settings or Values

This example explains changing C1-02 (Deceleration Time 1) from 10.0 seconds (default) to 20.0 seconds.

Step

Display/Result

1. Turn on the power to the drive. The initial display appears.

- MODE -

U1-01= 0.00Hz
U1-02= 0.00Hz

U1-03= 0.00A

DRV

FREF (OPR)

Rdy

JOG

FWD

FWD/REV

LSEQ

LREF

2. Press

or

until the Parameter Setting Mode screen appears.

HELP

- MODE -

PRG

DATA

Programming

FWD

3. Press

to enter the parameter menu tree.

-PRMSET-

Initialization

Select Language

PRG

FWD

A

1-00= 0

4. Press

or

to select the C parameter group.

-PRMSET-

Basic Setup

Accel Time 1

PRG

FWD

C

1-01=

10.0 sec

5. Press

two times.

-PRMSET-

Accel/Decel

Accel Time 1

PRG

C

1

-01=

10.0 sec

-PRMSET-

C1-

01

= 10.0Sec

(0.0~6000.0)

“10.0 sec”

PRG

Accel Time 1

FWD

FWD

4.3 The Drive, Programming, and Clock Adjustment Modes

118

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual