5.1 A: Initialization

The initialization group contains parameters associated with initial drive setup, including parameters involving the display

language, access levels, initialization, and password.

u

A1: Initialization

n

A1-00: Language Selection

Selects the display language for the digital operator.

Note:

This parameter is not reset when the drive is initialized using parameter A1-03.

No.

Parameter Name

Setting Range

Default

A1-00

Language Selection

0 to 7

0

Setting 0: English

Setting 1: Japanese

Setting 2: German

Setting 3: French

Setting 4: Italian

Setting 5: Spanish

Setting 6: Portuguese

Setting 7: Chinese

n

A1-01: Access Level Selection

Allows or restricts access to drive parameters.

No.

Parameter Name

Setting Range

Default

A1-01

Access Level Selection

0 to 2

2

Setting 0: Operation only

Access to only parameters A1-01, A1-04, and all U monitor parameters.

Setting 1: User Parameters

Access to only a specific list of parameters set to A2-01 through A2-32. These User Parameters can be accessed using the

Setup Mode of the digital operator.

Setting 2: Advanced Access Level (A) and Setup Access Level (S)

All parameters can be viewed and edited.

Notes on Parameter Access

• If the drive parameters are password protected by A1-04 and A1-05, parameters A1-00 through A1-03, A1-06, and all A2

parameters cannot be modified.

• If a digital input terminal programmed for “Program lockout” (H1-oo = 1B) is enabled, parameter values cannot be

modified, even if A1-01 is set to 1 or 2.

• If parameters are changed via serial communication, it will not be possible to edit or change parameter settings with the

digital operator until an Enter command is issued to the drive from the serial communication.

n

A1-03: Initialize Parameters

Resets parameters to default values or performs an Application Preset for fan or pump applications. After initialization, the

setting for A1-03 automatically returns to 0.

No.

Parameter Name

Setting Range

Default

A1-03

Initialize Parameters

0, 1110, 2220, 3330, 5550,

8008, 8009, 8010, 8011

0

5.1 A: Initialization

142

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual