Setting 51: Sequence Timer 1 Active

Sequence Timer 1 is active.

Setting 52: Sequence Timer 2 Active

Sequence Timer 2 is active.

Setting 53: Sequence Timer 3 Active

Sequence Timer 3 is active.

Setting 54: Sequence Timer 4 Active

Sequence Timer 4 is active.

Setting 58: Underload Detection

Underload is detected when the output current falls below the underload detection level defined by L6-14 and L6-02.

Setting 60: Internal Cooling Fan Alarm

The output closes when the drive internal cooling fan has failed.

Setting 71: Secondary PI Feedback Low

The PI2 feedback level is too low.

Setting 72: Secondary PI Feedback High

The PI2 feedback level is too high.

Setting 100 to 192: Functions 0 to 92 with Inverse Output

These settings have the same function as settings 0 to 92 but with inverse output. Set as 1oo, where the “1” indicates inverse

output and the last two digits specify the setting number of the function.
Examples:
• For inverse output of “8: During baseblock”, set 108.
• For inverse output of “4A: During KEB” set 14A.

n

H2-06: Watt Hour Output Unit Selection

When one of the multi-function terminals is set to output the number of watt hours (H2-01, H2-02, or H2-03 = 39), parameter

H2-06 determines the units for the output signal.
This output function provides a watt hour meter or a PLC input by a 200 ms pulse signal. H2-06 determines the frequency that

pulses are issued to keep track of the kWh for the drive.

No.

Parameter Name

Setting Range

Default

H2-06

Watt Hour Output Unit Selection

0: 0.1 kWh units

1: 1 kWh units

2: 10 kWh units

3: 100 kWh units

4: 1000 kWh units

0

Note:

1. A negative power output (i.e., regeneration) does not subtract from the total watt hours.
2. The drive keeps track of the watt hours as long as the control circuit has power. The value is reset when the power supply is shut off.

0.2 s

H2-06

(Pulse Output Unit)

H2-01 to 03

(Multi-function Output)

Integral Power (every 100 ms)

OFF

OFF

ON

Figure 5.57 Watt Hour Output Example

5.7 H: Terminal Functions

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

223

5

Parameter Details