beautypg.com

Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 393

background image

UL recognized electronic thermal overload function of the drive: Speed-dependent heat characteristics are simulated using

data from standard motors and force-ventilated motors. The motor is protected from overload using this function.

Using a Single Drive to Operate Multiple Motors

Set parameter L1-01 to 0 to disable thermal overload protection for the drive.

Note:

The UL recognized electronic thermal overload function cannot be applied when operating multiple motors with a single drive.

Long Motor Cables

When a high carrier frequency and long motor cables are used, nuisance tripping of the thermal relay may occur due to increased

leakage current. To avoid this, reduce the carrier frequency or increase the tripping level of the thermal overload relay.

Nuisance Tripping Due to a High AC Drive Carrier Frequency

Current waveforms generated by high carrier frequency PWM drives tend to increase the temperature in overload relays. It

may be necessary to increase the trip level setting when encountering nuisance triggering of the relay.

WARNING!

Fire Hazard. Confirm an actual motor overload condition is not present prior to increasing the thermal oL trip setting. Check

local electrical codes before making adjustments to motor thermal overload settings. Failure to comply could result in death or serious injury.

8.5 Installing Peripheral Devices

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

393

8

Peripheral Devices & Options

This manual is related to the following products: