Name

Setting Range

Default

L3-23

Automatic Reduction Selection for Stall Prevention During Run

0, 1

0

Setting 0: Disabled

The level set in L3-06 is used throughout the entire speed range.

Setting 1: Enabled

The Stall Prevention level during run is reduced in the constant power range. The lower limit will be 40% of L3-06.

n

L3-24: Motor Acceleration Time for Inertia Calculations

Sets the time to accelerate the motor from stop to the maximum speed at motor rated torque. Set this parameter when using

Single Drive KEB 2 (L2-29 = 1), Intelligent Stall Prevention during Deceleration (L3-04 = 2), or the Overvoltage Suppression

function (L3-11 = 1).

No.

Name

Setting Range

Default

L3-24

Motor Acceleration Time for Inertia Calculations

0.001 to 10.000 s

Determined by o2-04

<1>

<1> Parameter L3-24 is defaulted for a Yaskawa standard 4-pole motor. During Auto-Tuning, L3-24 will be initialized to a Yaskawa standard 4-pole

motor if parameter E2-11 is changed.

Manual Parameter Setup

Make the calculations in the formula below:

L3-24 =

2 J [kgm

2

] n

[r/min]

60 T

[Nm]

rated

rated

Calculate the rated torque in the formula below:

60 P

[kW] 10

3

2

n

[r/min]

T

[Nm] =

Motor

rated

rated

n

L3-25: Load Inertia Ratio

Determines the ratio between the rotor inertia and the load. Set this parameter when using Single Drive KEB 2 (L2-29 = 1),

Intelligent Stall Prevention during deceleration (L3-04 = 2), or the overvoltage suppression function (L3-11 = 1).

No.

Name

Setting Range

Default

L3-25

Load Inertia Ratio

1.0 to 1000.0

1.0

When set incorrectly, a fairly large current ripple can result during Single Drive KEB 2 (L2-29 = 1). This may cause overvoltage

suppression (L3-11 = 1) or other faults such as ov, Uv1, and oC.

Manual Parameter Setup

Calculate parameter L3-25 in the formula below:

L3-25 =

Machine Inertia

Motor Inertia

n

L3-26: Additional DC Bus Capacitors

Sets the capacity of any additionally installed DC bus capacitors. This data is used in calculations for Single Drive KEB Ride-

Thru 2. Adjust this setting only if external capacity is connected to the DC bus and Single Drive KEB 2 is used.

No.

Name

Setting Range

Default

L3-26

Additional DC Bus Capacitors

0 to 65000 μF

0 μF

n

L3-27: Stall Prevention Detection Time

Sets a delay time from when the Stall Prevention level is reached and the actual Stall Prevention function is activated.

No.

Name

Setting Range

Default

L3-27

Stall Prevention Detection Time

0 to 5000 ms

50 ms

5.8 L: Protection Functions

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

251

5

Parameter Details