Yaskawa AC Drive-P1000 Industrial Fan User Manual
Page 279

No.
Name
Setting Range
Default
S2-01
Sequence Timer 1 Start Time
00:00 to 24:00
00:00
S2-06
Sequence Timer 2 Start Time
00:00 to 24:00
00:00
S2-11
Sequence Timer 3 Start Time
00:00 to 24:00
00:00
S2-16
Sequence Timer 4 Start Time
00:00 to 24:00
00:00
n
S2-02/S2-07/S2-12/S2-17: Sequence Timers 1 to 4 Stop Time
Sets the stop times for timers 1 to 4. The values must be set greater than or equal to S2-01/S2-06/S2-11/S2-16.
No.
Name
Setting Range
Default
S2-02
Sequence Timer 1 Stop Time
00:00 to 24:00
00:00
S2-07
Sequence Timer 2 Stop Time
00:00 to 24:00
00:00
S2-12
Sequence Timer 3 Stop Time
00:00 to 24:00
00:00
S2-17
Sequence Timer 4 Stop Time
00:00 to 24:00
00:00
n
S2-03/S2-08/S2-13/S2-18: Sequence Timers 1 to 4 Day Selection
Sets the days for which sequence timers 1 to 4 are active.
No.
Name
Setting Range
Default
S2-03
Sequence Timer 1 Day Selection
0 to 10
0
S2-08
Sequence Timer 2 Day Selection
0 to 10
0
S2-13
Sequence Timer 3 Day Selection
0 to 10
0
S2-18
Sequence Timer 4 Day Selection
0 to 10
0
Setting 0: Timer Disabled
Setting 1: Daily
Setting 2: Mon - Fri
Setting 3: Sat - Sun
Setting 4: Monday
Setting 5: Tuesday
Setting 6: Wednesday
Setting 7: Thursday
Setting 8: Friday
Setting 9: Saturday
Setting 10: Sunday
n
S2-04/S2-09/S2-14/S2-19: Sequence Timers 1/2/3/4 Selection
Sets the action that occurs when sequence timers 1 to 4 are active.
No.
Name
Setting Range
Default
S2-04
Sequence Timer 1 Selection
0 to 2
0
S2-09
Sequence Timer 2 Selection
0 to 2
0
S2-14
Sequence Timer 3 Selection
0 to 2
0
S2-19
Sequence Timer 4 Selection
0 to 2
0
Setting 0: Digital Output Only
Setting 1: Run
Setting 2: Run - PI Disable
n
S2-05/S2-10/S2-15/S2-20: Sequence Timers 1/2/3/4 Reference Source
Selects the frequency reference source used for running the drive when sequence timers 1 to 4 are active (only applicable when
S2-04/S2-09/S2-14/S2-19 are set to 1 or 2).
5.11 S: Special Application
YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual
279
5
Parameter Details