Setting 1: -10 to 10 Vdc

The input level is -10 to 10 Vdc.

Refer to Setting 1: 0 to 10 Vdc Bipolar on page 224

.

Setting 2: 4 to 20 mA

The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.

Setting 3: 0 to 20 mA

The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.

n

H3-10: Terminal A2 Function Selection

Determines the function assigned to analog input terminal A2.

Refer to Multi-Function Analog Input Terminal Settings on

page 227

for a list of functions and descriptions.

No.

Name

Setting Range

Default

H3-10

Terminal A2 Function Selection

0 to 26

0

n

H3-11, H3-12: Terminal A2 Gain and Bias Setting

Parameter H3-11 sets the level of the input value selected that is equal to 10 Vdc input or 20 mA input to terminal A2.
Parameter H3-12 sets the level of the input value selected that is equal to 0 V, 4 mA or 0 mA input at terminal A2.
Use both parameters to adjust the characteristics of the analog input signal to terminal A2. The setting works in the same way

as parameters H3-03 and H3-04 for analog input A1.

No.

Name

Setting Range

Default

H3-11

Terminal A2 Gain Setting

-999.9 to 999.9%

100.0%

H3-12

Terminal A2 Bias Setting

-999.9 to 999.9%

0.0%

n

H3-13: Analog Input Filter Time Constant

Parameter H3-13 sets the time constant for a first order filter that will be applied to the analog inputs.
An analog input filter prevents erratic drive control when using a “noisy” analog reference. Drive operation becomes more

stable as the programmed time becomes longer, but it also becomes less responsive to rapidly changing analog signals.

No.

Name

Setting Range

Default

H3-13

Analog Input Filter Time Constant

0.00 to 2.00 s

0.03 s

n

H3-14: Analog Input Terminal Enable Selection

When one of the multi-function digital input parameters is set for “Analog input enable” (H1-oo = C), the value set to H3-14

determines which analog input terminals are enabled when the input is closed. All of the analog input terminals will be enabled

all of the time when H1-oo

≠ C. The terminals not set as the target are not influenced by input signals.

No.

Name

Setting Range

Default

H3-14

Analog Input Terminal Enable Selection

1 to 7

7

Setting 1: A1 Only Enabled

Setting 2: A2 Only Enabled

Setting 3: A1 and A2 Only Enabled

Setting 4: A3 Only Enabled

Setting 5: A1 and A3 Only Enabled

Setting 6: A2 and A3 Only Enabled

Setting 7: All Analog Input Terminals Enabled

n

H3-16 to H3-18: Terminal A1/A2/A3 Offset

Set the offset level of the selected input value to terminals A1, A2, or A3 that is equal to 0 Vdc input. These parameters rarely

require adjustment.

5.7 H: Terminal Functions