L3: stall prevention – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 246

background image

No.

Name

Setting Range

Default

L2-11

DC Bus Voltage Setpoint during KEB

150 to 400 Vdc

<1>

[E1-01] × 1.22

<1> Values are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives, but set the

value below 1040 Vdc (overvoltage protection level).

n

L2-29: KEB Method Selection

Selects the way the Kinetic Energy Buffering function operates.

Note:

If a multi function input is set for Single KEB Ride-Thru 2 (H1-oo = 7A, 7B), the setting of L2-29 is disregarded and the KEB mode equal

to L2-29 = 1 is automatically selected.

No.

Name

Setting Range

Default

L2-29

KEB Method Selection

0 to 3

0

Setting 0: Single Drive KEB Ride-Thru 1

Setting 1: Single Drive KEB Ride-Thru 2

Setting 2: System KEB Ride-Thru 1

Setting 3: System KEB Ride-Thru 2

Refer to KEB Ride-Thru Function on page 240

for detailed explanations.

u

L3: Stall Prevention

The motor may experience excessive slip because it cannot keep up with the frequency reference when the load is too high or

acceleration and deceleration times are too short. If the motor slips during acceleration, it usually causes an overcurrent fault

(oC), drive overload (oL2), or motor overload (oL1). If the motor slips during deceleration, it can cause excessive regenerative

power to flow back into the DC bus capacitors, and eventually cause the drive to fault out from overvoltage (oV). The Stall

Prevention Function prevents the motor from stalling and while allowing the motor to reach the desired speed without requiring

the user to change the acceleration or deceleration time settings. The Stall Prevention function can be set separately for

acceleration, operating at constant speeds, and deceleration.

n

L3-01: Stall Prevention Selection during Acceleration

Stall Prevention during acceleration prevents tripping with overcurrent (oC), motor overload (oL1), or drive overload (oL2)

faults common when accelerating with heavy loads.
L3-01 determines the type of Stall prevention the drive should use during acceleration.

No.

Name

Setting Range

Default

L3-01

Stall Prevention Selection during Acceleration

0 to 2

1

Setting 0: Disabled

No Stall Prevention is provided. If the acceleration time is too short, the drive may not be able to get the motor up to speed

fast enough, causing an overload fault.

Setting 1: Enabled

Enables Stall Prevention during acceleration.
Acceleration is reduced when the output current value exceeds 85% of the level set to parameter L3-02 for a longer than the

time set to L3-27. The acceleration stops when the current exceeds L3-02. Acceleration continues when the current falls below

L3-02 for longer than the time set to L3-27.
The Stall Prevention level is automatically reduced in the constant power range.

Refer to L3-03: Stall Prevention Limit during

Acceleration on page 247

.

5.8 L: Protection Functions

246

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual