L8-38: Carrier Frequency Reduction Selection

Selects the operation of the carrier frequency reduction function. Reduces the carrier frequency when the output current exceeds

a certain level. This temporarily increases the overload capability (oL2 detection), allowing the drive to run through transient

load peaks without tripping.

No.

Name

Setting Range

Default

L8-38

Carrier Frequency Reduction Selection

0 to 2

2

Setting 0: Disabled

No carrier frequency reduction at high current.

Setting 1: Enabled for output frequencies below 6 Hz

The carrier frequency is reduced at speeds below 6 Hz when the current exceeds 100% of the drive rated current. The drive

returns to the normal carrier frequency when the current falls below 88% or the output frequency exceeds 7 Hz.

Setting 2: Enabled for entire frequency range

The carrier frequency is reduced at the following speeds:
• Below 6 Hz when the current exceeds 100% of the drive rated current.
• Above 7 Hz when the current exceeds 112% of the drive rated current.
The drive uses the delay time set in parameter L8-40 and a hysteresis of 12% when switching the carrier frequency back to

the set value.

n

L8-40: Carrier Frequency Reduction Off-Delay Time

Sets a hold time before returning to the original carrier frequency setting after the carrier frequency has been temporarily

derated as determined by L8-38. The carrier frequency reduction function is disabled when this value is 0.00 s.

No.

Name

Setting Range

Default

L8-40

Carrier Frequency Reduction Off-Delay Time

0.00 to 2.00 s

0.50 s

n

L8-41: High Current Alarm Selection

Triggers a high current alarm (HCA) when the output current exceeds 150% of the drive rated current.

No.

Name

Setting Range

Default

L8-41

High Current Alarm Selection

0, 1

0

Setting 0: Disabled

No alarm is detected.

Setting 1: Enabled

An alarm is triggered when the output current exceeds 150% of the drive rated current. A digital output set for an alarm

(H2-oo = 10) will close.

n

L8-55: Internal Braking Transistor Protection

Enables or disables protection for the internal braking transistor.

Note:

This parameter is not available in models 4A0930 and 4A1200.

No.

Name

Setting Range

Default

L8-55

Internal Braking Transistor Protection

0, 1

1

Setting 0: Disabled

Disable braking transistor protection when not using the internal braking transistor, including the following instances:
• When using a regen converter such as DC5.
• When using a regen unit such as RC5.
• When using external braking transistor options like CDBR units.
• When using the drive in common DC bus applications and the internal braking unit is not installed.
Enabling L8-55 under such conditions can incorrectly trigger a braking transistor fault (rr).

Setting 1: Enabled

Enable L8-55 when connecting a braking resistor or a braking resistor unit to the drive built-in braking transistor.

5.8 L: Protection Functions

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

261