A.4 Monitoring Parameter Alarms
A-37
A
A.4.2
Monitoring Parameter Number 23 Alarms
The following table shows the servo-related alarms for each axis.
Register
Number
Bit
Alarm Name
Cause
Action
IL22
b0:
Not used
−
−
b1: OTF
Forward Overtravel
• Forward overtravel of the SERVO-
PACK was detected (P-OT signal
ON).
• Check the overtravel limit switch,
and bring it back in the opposite
direction after resetting the alarm.
• Check the overtravel input signal.
• Check the parameters relating to
overtravel alarm detection.
b2: OTR
Reverse Overtravel
• Reverse overtravel of the SERVO-
PACK was detected (N-OT signal
ON).
• Check the overtravel limit switch,
and bring it back in the opposite
direction after resetting the alarm.
• Check the overtravel input signal.
• Check the parameters relating to
overtravel alarm detection.
b3: SOTF
Positive Software
Limit
• Movement towards the positive
software limit area was detected.
• After checking the program and
operation, reset the alarm and
bring the switch back in the oppo-
site direction.
• Check the parameters relating to
the software limit.
b4: SOTR
Negative Software
Limit
• Movement towards the negative
software limit area was detected.
• After checking the program and
operation, reset the alarm and
bring the switch back in the oppo-
site direction.
• Check the parameters relating to
the software limit.
b5:
Not used
−
−
b6:
TIMEOVER
Positioning time
exceeded
• After the command was executed,
positioning could not be com-
pleted in the time set in
OW34 (Positioning Com-
pleted Check Time).
• Check the parameters relating to
the servo characteristics (each
gain setting).
• Check the connections between
the SERVOPACK and motors.
b7:
Not used
−
−
b8:
Not used
−
−
b9:
Not used
−
−
b10:
Not used
−
−
b11:
SET_NRDY
No Zero Point
• No zero point has been set.
• Set the zero point.
b12 to b16:
Not used
−
−
b18:
PGLEFT
Broken PG Wiring
• Encoder wiring is faulty or broken.
• Encoder or SERVOPACK is
faulty.
• SVA Module is faulty.
• Check the encoder wiring.
• Contact your Yaskawa sales repre-
sentative.
b19:
Not used
−
−