4 Motion Control

4.4.4 Zero Point Return (ZRET)

4-58

„

DEC2 + C-phase Pulse

This method is used to perform zero point return using a limit switch (deceleration limit
switch) and a zero point signal (C-phase pulse) by rapid traverse using linear acceleration/
deceleration (without a dog width).

This method can be used in the mechanical configuration with the limit switch as shown in

the illustration below.

1. With this method, the axis recognizes the machine position by the deceleration limit switch ON/OFF

status, and automatically performs a return operation. Be sure to perform zero point return under the
same conditions.

2. With pattern (B), set the deceleration limit switch inversion selection (bit 10) of motion fixed

parameter No. 17 to ON.

Zero Point Return Operation Started with the Dog (Deceleration Limit
Switch) Signal in the High Area

Pattern (A)

Pattern (B)

SVA-01A

SVA-02A

SVB-01

PO-01

Applicable

Applicable

N/A

N/A

High

Low

Deceleration
limit switch

Machine total
operating area

Reverse direction

Forward direction

High

Low

Deceleration
limit switch

Reverse direction

Forward direction

Machine total
operating area

INFO

0

1.

2.

5.

4.

3.

6.

Reverse direction

← → Forward direction

Zero point

Speed
reference

Rapid traverse speed

Approach speed

Creep speed

Zero point
return position

Dog
(Deceleration limit switch)

Zero point signal
(C-phase pulse)

Zero point return
final travel distance

Time