Yaskawa MP920 User's Manual Design User Manual
Page 506
12 Troubleshooting
12.2.4 System Register Configuration
12-16
■
System I/O Error Status
Actions to be Taken when a Transmission Error Occurs
When a transmission error occurs during system I/O, the error status is reported in the sys-
tem register as shown below.
Name
Register No.
Remarks
I/O Error Count
SW00200
Number of I/O errors
Input Error Count
SW00201
Number of input errors
Input Error Address
SW00202
Latest input error address (For
future use)
(Register number of OW)
Output Error Count
SW00203
Number of output errors
Output Error Address
SW00204
Latest input error address (For
future use)
(Register number of OW)
Reserved by System
SW00205
(Not used)
SW00206
SW00207
I/O Error Status
SW00208 to
SW00211
Slot 2 error status
SW00212 to
SW00215
Slot 3 error status
:
:
SW00420 to
SW00423
Slot 55 error status
Name
Register Number
Remarks
Slot 2 Error Status
SW00208 to SW00211
Differs depending on the Module
mounted.
Slot 3 Error Status
SW00212 to SW00215
Differs depending on the Module
mounted.
:
:
Slot 55 Error Status
SW00420 to SW00423
Differs depending on the Module
mounted.
- Tag Generator (30 pages)
- MP3300iec (82 pages)
- 1000 Hz High Frequency (18 pages)
- 1000 Series (7 pages)
- PS-A10LB (39 pages)
- iQpump Micro User Manual (300 pages)
- 1000 Series Drive Option - Digital Input (30 pages)
- 1000 Series Drive Option - CANopen (39 pages)
- 1000 Series Drive Option - Analog Monitor (27 pages)
- 1000 Series Drive Option - CANopen Technical Manual (37 pages)
- 1000 Series Drive Option - CC-Link (38 pages)
- 1000 Series Drive Option - CC-Link Technical Manual (36 pages)
- 1000 Series Drive Option - DeviceNet (37 pages)
- 1000 Series Drive Option - DeviceNet Technical Manual (81 pages)
- 1000 Series Drive Option - MECHATROLINK-II (32 pages)
- 1000 Series Drive Option - Digital Output (31 pages)
- 1000 Series Drive Option - MECHATROLINK-II Technical Manual (41 pages)
- 1000 Series Drive Option - Profibus-DP (35 pages)
- AC Drive 1000-Series Option PG-RT3 Motor (36 pages)
- Z1000U HVAC MATRIX Drive Quick Start (378 pages)
- 1000 Series Operator Mounting Kit NEMA Type 4X (20 pages)
- 1000 Series Drive Option - Profibus-DP Technical Manual (44 pages)
- CopyUnitManager (38 pages)
- 1000 Series Option - JVOP-182 Remote LED (58 pages)
- 1000 Series Option - PG-X3 Line Driver (31 pages)
- SI-EN3 Technical Manual (68 pages)
- JVOP-181 (22 pages)
- JVOP-181 USB Copy Unit (2 pages)
- SI-EN3 (54 pages)
- SI-ET3 (49 pages)
- MECHATROLINK-III (35 pages)
- EtherNet/IP (50 pages)
- SI-EM3 (51 pages)
- 1000-Series Option PG-E3 Motor Encoder Feedback (33 pages)
- 1000-Series Option SI-EP3 PROFINET (56 pages)
- PROFINET (62 pages)
- AC Drive 1000-Series Option PG-RT3 Motor (45 pages)
- SI-EP3 PROFINET Technical Manual (53 pages)
- A1000 Drive Option - BACnet MS/TP (48 pages)
- 120 Series I/O Modules (308 pages)
- A1000 12-Pulse (92 pages)
- A1000 Drive Software Technical Manual (16 pages)
- A1000 Quick Start (2 pages)
- JUNMA Series AC SERVOMOTOR (1 page)
- A1000 Option DI-101 120 Vac Digital Input Option (24 pages)