Details – Yaskawa MP920 User's Manual Design User Manual
Page 130
4 Motion Control
4.2.4 Phase Control Mode
4-16
Details
Use the following procedure to perform phase control operation.
1. Set the motion fixed parameters according to the user’s machine.
* 1. Valid only with an SVB-01 Module.
* 2. Valid only with an SVA-02A Module.
2. Set the motion parameters. Use the user program to control the reference speed so that no
shock occurs.
The following three methods can be used to set the setting parameters.
• Using the MPE720 Setting Parameter Window
• Using a ladder logic program
• Using a motion program
Table 4.5 shows the related parameters when the phase control mode is used.
Table 4.4 Examples of Fixed Parameters
No.
Name
Setting Range
Meaning
Setting Example
7
Rated Motor Speed
Setting
1 to 32000
Rated motor speed
3000 r/min
8
Number of Feedback
Pulses per Motor Rotation
4 to 65532
Number of pulses
before multiplica-
tion
2048 pulses/rev
9
D/A Output Voltage at
100% Speed
0.001 to 10.000
1 = 1 V
6.000 V
Feedback Pulses per
Motor Rotation
(for High-resolution)
*1
4 to 2147483647 1 = 1 pulse/rev
2048 pulses/rev
10 D/A Output Voltage at
100% Torque Limit
*2
0.001 to 10.000
0.001 = 0.001 V
1 = 1 V
3.000 V
1. Set the motion fixed parameters.
2. Set the motion setting parameters.
3. Select the phase control mode (PHCON).
4. Set the RUN command (RUN) to ON.
PCON
RUN
0
5. Set the phase control mode to OFF.
(100%)
Phase control operation is performed.
Time (t)
Speed (%)
Reference
speed
Position
: System execution
: User settings