A.4 monitoring parameter alarms – Yaskawa MP920 User's Manual Design User Manual
Page 551
Appendix A
A.4.1 Setting Errors in Fixed and Setting Parameters
A-36
A.4
Monitoring Parameter Alarms
This section describes the monitoring parameter alarms, together with their causes and correc-
tive actions to be taken.
A.4.1
Setting Errors in Fixed and Setting Parameters
The following table shows the parameter No.1 operation status (bit 1 and bit 2).
The parameter number in which the setting range error has occurred can be identified using
IW0F (Parameter Number Out of Range).
Register Number
Bit
Alarm Name
Cause
Action
IW00
b1: PRMERR
Setting
Parameter
Setting Error
A setting that exceeds the setting
range has been made in a setting
parameter.
Reset the setting parameter.
b2: FPRMERR
Fixed Parameter
Setting Error
A setting that exceeds the setting
range has been made in a fixed
parameter.
Reset the fixed parameter.
Parameter Number
Name
Register Number
Description
Remarks
11
Parameter Number
Out of Range
IW0F
• When a setting that exceeds the setting
range has been made in a fixed parame-
ter or a setting parameter, the last
parameter number in which a setting
range error occurred is stored.
• Setting parameters: 1 to 47
• Fixed parameters: 101 to 127