A.4 monitoring parameter alarms – Yaskawa MP920 User's Manual Design User Manual

Page 551

background image

Appendix A

A.4.1 Setting Errors in Fixed and Setting Parameters

A-36

A.4

Monitoring Parameter Alarms

This section describes the monitoring parameter alarms, together with their causes and correc-
tive actions to be taken.

A.4.1

Setting Errors in Fixed and Setting Parameters

The following table shows the parameter No.1 operation status (bit 1 and bit 2).

The parameter number in which the setting range error has occurred can be identified using
IW††0F (Parameter Number Out of Range).

Register Number

Bit

Alarm Name

Cause

Action

IW††00

b1: PRMERR

Setting
Parameter
Setting Error

A setting that exceeds the setting
range has been made in a setting
parameter.

Reset the setting parameter.

b2: FPRMERR

Fixed Parameter
Setting Error

A setting that exceeds the setting
range has been made in a fixed
parameter.

Reset the fixed parameter.

Parameter Number

Name

Register Number

Description

Remarks

11

Parameter Number
Out of Range

IW††0F

• When a setting that exceeds the setting

range has been made in a fixed parame-
ter or a setting parameter, the last
parameter number in which a setting
range error occurred is stored.

• Setting parameters: 1 to 47
• Fixed parameters: 101 to 127