5 Modules

5.6.4 DeviceNet Interface Module (260IF)

5-130

„

Rotary Switches SW2 and SW3

The SW2 and SW3 are used to set the MAC ID of the DeviceNet.

„

LED Indicators

The following table shows the LED indicator display patterns.

* 1. Offline status: Status from the time the LED test after startup com-

pletes to the time the MAC ID duplication check completes (2 sec-
onds)
Online status: Status after the MAC ID duplication check completes at
startup

* 2. If a DeviceNet bus OFF error occurs due to disconnection from the

power supply, the 260IF Module executes the Automatic Reset opera-
tion according to the DeviceNet specifications. In this case, the NS
lights up in red in a instant, then lights out. When the network power
supply is restored, the NS will start blinking in green (no connection
being established in online).

The 260IF executes the MS and NS LED check for one second when the power is turned ON
according to the DeviceNet Specifications. The following figure shows the LED display
during the LED test.

Table 5.10 Rotary Switches SW2 and SW3

Name

Meaning

Setting

*10 (SW2)

MACID 10s digit

0 to 6

Use these two rotary switches to set the node
MAC ID in decimal between 0 and 63.
(Factory setting: 00)

*1 (SW3)

MACID 1s digit

0 to 9

Table 5.11 LED Indicator Display Patterns

Name

Display

Status

Meaning

MS

2-color LED

(red/green)

Unlit
Lit in green
Lit in red

Module power supply disconnected
Normal operation
Self-diagnosis error/Watchdog timeout error

NS

2-color LED

(red/green)

Unlit
Green blinking
Lit in green
Red blinking
Lit in red

Module power supply disconnected/Offline status

*1

No connection being established in online status
Connection being established in online status
No DeviceNet communications
Communications disabled (duplicated MAC ID)/Bus
OFF
Watchdog timeout error

*2