4 system register configuration, System status – Yaskawa MP920 User's Manual Design User Manual
Page 499
12.2 System Errors
12-9
12
12.2.4
System Register Configuration
System Status
System status indicates the operating status and error details for the system. System status
details are used to determine whether hardware or software is the cause of an error.
Table 12.1 System Status List
Name
Register
No.
Contents
Reserved for
the System
SW00030 to
SW00039
(Not used)
CPU Status
SW00040
SB000400
READY
1: Normal,
0: Communications/Self-diagnosis error
SB000401
RUN
1: Running, 0: Stopped
SB000402
ALARM
1: Alarm, 0: Normal
SB000403
ERROR
1: Error, 0: Normal
SB000404
RESUME
1: Continued startup operation
0: New startup operation
SB000405
Start status
1: Restoration from power interruption
0: Ordinary restoration
SB000406
Reserved by system.
(Not used)
SB000407
WEN
1: WRITE enabled, 0: WRITE disabled
SB000408
Reserved by system.
−
SB000409
MASTER
1: Control system CPU, 0: Standby system
SB00040A
Reserved by system.
(Not used)
SB00040B
SB00040C
SB00040D
SB00040E
Operation stop request
1: STOP selection, 0: RUN selection
SB00040F
Reserved by system.
(Not used)
CPU Error
Status
SW00041
SB000410
Serious failure
1: WDGE, undefined command
See SW00050 for more details.
SB000411
Program memory error
1: Program memory error
SB000412
Calendar IC error
1: Calendar IC error
SB000413
Reserved by system.
(Not used)
SB000414
SB000415
SB000416
SB000417
SB000418
User operation error
1: User operation error
SB000419
I/O error
1: I/O error
SB00041A to
SB00041F
Reserved by system.
(Not used)