Rotary switches, Dip switch (sw3) – Yaskawa MP920 User's Manual Design User Manual
Page 321

5 Modules
5.6.3 215IF Communications Module (215IF)
5-126
Rotary Switches
The SW1 and SW2 are used to set the station address on the 215IF transmission. The SW1
sets the 1s digit (
×1) and the SW2 sets the 10s digit (×10). Set a station address between 1
and 64. The SW1 and SW2 are valid only when the INIT of SW3 is set to ON.
DIP Switch (SW3)
The SW3 is used to set the operation mode such as transmission speed and self-diagnosis.
All the pins of SW3 are set by default to OFF (to the right).
INIT Pin of DIP Switch SW3
When the power is turned ON with the INIT pin set to ON, the 215IF Module executes message com-
munications according to the station addresses set by SW1 and SW2, the transmission speed set by
BRS0 and BRS1 of SW3, and the network address set by SW4. In this case, the link communication is
not executed and the relay function is disabled.
When the power is turned ON with the INIT pin set to OFF, the 215IF Module executes the link com-
munications and message communications according to the settings in the Module Condiguration Def-
inition Window of the MPE720. In this case, the settings of SW1, SW2, BRS0 and BRS1 of SW3, and
SW4 will be ignored.
To perform engineerings such as programming and register display on the MPE720 using the 215IF
Module when no module configuration definition is set, set the INIT pin to ON. Set the INIT pin to
ON only when forcibly communicating with the MPE720 such as when the CPU memory is cleared.
Indicator
Name
Setting
Function
ADRS
× 1
ADDRESS
× 1
0 to 6
Sets the station address 1s
digit.
ADRS
× 10
ADDRESS
×
10
0 to 6
Sets the station address 10s
digit.
SW1
SW2
ADRS
X1
ADRS
X10
Pins
Name
Setting
Operation
BRS0
Baud Rate
Select 0
ON
Transmission speed setting
(Valid only when the INIT is set to ON)
OFF
Transmission
speed (bps)
4M
2M
1M
−
BRS1
Baud Rate
Select 1
ON
BRS0
ON OFF ON OFF
OFF
BRS1
ON ON OFF OFF
INIT
INITIAL
ON
SW1, SW2, and BRS0 and BRS1 of SW3 are
valid.
OFF
Depends on the CPU transmission parameter set-
ting (software setting).
TEST
TEST
ON
Offline self-diagnosis mode
OFF
Normal operation mode
ON
SW3
ON
OFF
BRS0
BRS1
INIT
TEST
INFO