Addressing syntax for Allen–Bradley programmable controllers

D–29

SoftLogix 5 timer, counter, control, SFC

status, message, PID, block transfer, and

token data files

FFnnnn:eeee.MNE[ss]/bb

FF

File type:
T = Timer
C = Counter
R = Control
SC = SFC status
MG = Message
PD = PID control
BT = Block transfer
TD = Token data

nnnn

File number: 3 – 4095 decimal
For direct driver communication, timer, counter,
and control file types use the default file number
if the file number is absent. The default numbers
are 4 (timer), 5 (counter), and 6 (control).

eeee

Element number: 0 – 4095 decimal

MNE

Member mnemonic (see mnemonic tables
starting on page D-30)

ss

Submember
Only applies to .ADDR and .DATA members of
PID structure and .DATA member of
MSG structure.

bb

(optional

)

Bit number: 0 – 15 decimal
Only applies to analog word members.

Example: MG4095:3000.DATA[0]/15