Tag monitor—Use the tag monitor to check the communication

status for a device tag. The states are:

Disabled if the node has been disabled in the Node editor or

disabled using the NodeDisable command

Error if RSView32 has tried to acquire a value but could not

because of some kind of communication error, such as a node
not being available or a DDE server not running

Stale if the tag value has been acquired before but does not

have an updated value

Uninitialized if the value has never been acquired

Valid if RSView32 has a valid value for the tag

None if there is a problem with the tag definition such as it is

not a valid tag type or if the tag database has been accessed with
a third–party tool such as Microsoft

®

Access. If the underlying

tag type is valid, editing and saving the tag and then redisplaying
the tag monitor will fix the problem.

System\com tags—Use the system\com tags to receive a more

detailed error message. If the tag monitor reports an error, move
to an empty cell in the tag monitor, type system\com* and, when
the dialog box appears, click Select All. For a complete list of
system\com tags, see Appendix B, System tags.