Addressing syntax for Allen–Bradley programmable controllers

D–13

In RSView32, the first physical module of each type (input or output)
is address slot number 0. The next module of the same type in the
next higher–numbered rack slot is address slot number 1, and so on.

Example: SLC 5 I/O module addressing

SLC

Type

Rack

Configuration

CV for MS-DOS

®

Address or

APS Address

RSView32

Address

Fixed
L40

I/O module slot 0
(fixed)

I:0.0 or I:0
I:0.1
O:0

I:0.0 or I:0
I:0.1 or I:1
O:0

I module slot 2

I:2

I:2

Fixed
L30

I/O module slot 0
(fixed)

I:0.0 or I:0
I:0.1
O:0

I:0.0 or I:0
I:0.1 or I:1
O:0

I module slot 1

I:1

I:2

O module slot 2

O:2

O:1

Fixed
L20

I/O module slot 0
(fixed)

I:0.0 or I:0
O:0

I:0.0 or I:0
O:0

I module slot 1

I:1

I:1

I module slot 2

I:2

I:2

Modula
r

CPU slot 0

N/A

N/A

O module slot 1

O:1

O:0

I module slot 2

I:2

I:0

O module slot 3

O:3

O:1