beautypg.com

Alarmlogremark [“text”] [/p] [/sn] [/r] [/ttagname – Rockwell Automation 9301 Series RSView32 Users Guide User Manual

Page 637

background image

RSView32 commands

A–17

AlarmLog

Remark

AlarmLogRemark [“Text”] [/P] [/Sn] [/R] [/Ttagname]

Adds the specified text string as a transaction in the alarm log file.

[“Text”]

A text string, up to 132 characters long. The text
can contain the following placeholders:

[\D]

the current date

[\T]

the current time

[\N]

the tag name. If the tag is in a local tag
database, you can also use the
placeholders [\S] tag description and
[\U] tag units.

[/P]

Prompts the operator for a remark at runtime by
displaying a dialog box containing a text box. The
operator can type a remark up to 132 characters long.
The remark can also include the placeholders shown
above.

If both the Text parameter and the /P parameter are
specified, the contents of the Text parameter will
appear in the text field at runtime, and the operator
can modify or add to the contents of the Text
parameter before it is logged to the alarm log file. If
the tag name (/T parameter) is specified, the prompt
dialog box will display the tag name at runtime, but
the operator cannot change the tag name.

[/Sn]

Associates an alarm severity with the remark. The
severity is an integer from 1 to 8. This value is shown
in the Severity column of the alarm log file. If the
remark is logged to a printer, the alarm severity
determines which printer will print the remark.

If both the /P parameter and the /Sn parameter are
specified, the prompt dialog box will display the