can configure thresholds 1, 2, 5, and 8 as long as you configure
them in that order.

3.

Fill in the fields as follows:

Threshold

To define a constant threshold, type a number. To define a variable
threshold, specify a tag name.

Increasing/Decreasing

To monitor for a rising value that passes the threshold, click
Increasing. To monitor for a falling value that passes the threshold,
click Decreasing.

Alarm Label

Type a description of the alarm up to 21 characters long. This
description is displayed in the alarm summary and alarm banner.

Severity

Select a severity level. Severity 1 is most severe, Severity 8 is least
severe.

Severities are configured in the Alarm Setup editor. For details, see
“Configuring alarm severity” on page 6-33.

In Alarm Messages

Select the message you want when the tag goes into alarm.

If you click Custom Message, type the message in the File and/or
Printer fields. You can use both words and placeholders.

For detailed information about messages, see “Configuring alarm
messages” on page 6-36.

At runtime a variable threshold must not become higher than
the threshold above it or lower than the threshold below it, or an
alarm fault will be generated for the tag.

IMPORTANT