Plc–5 data files, Plc–5 binary files: optional syntax – Rockwell Automation 9301 Series RSView32 Users Guide User Manual

Page 703

background image

Addressing syntax for Allen–Bradley programmable controllers

D–5

PLC–5 data files

Fnnn:eee/bb

F

File type:
B = Binary
N = Integer
D = Decimal (BCD)
F = Floating point
A = ASCII

nnn

File number: 3 – 999 decimal
For direct driver communication, binary, integer,
and floating point file types use the default file
number if the file number is absent. The default
numbers are 3 (binary), 7 (integer), and
8 (floating point).

eee

Element number: 0 – 999 decimal

bb

(optional)

Bit offset within word: 0 – 15 decimal
Not applicable to floating point file types.

Example of bit address: B3:173/15

Example of word address: N7:12

PLC–5 binary files: optional syntax

Fnnn/bbbbb

F

File type:
B = Binary

nnn

File number: 3 – 999 decimal
For direct driver communication, the default file
number 3 is used if the file number is absent.

bbbbb

Bit offset from start of file: 0 – 15999 decimal

Example: B3/1024