Configuring rslinx gateway, Configuring rslinx gateway -9 – Rockwell Automation 9301 Series RSView32 Users Guide User Manual
Page 601
Using networks
17–9
Access Path:
Bottling (optional)
Update Rate:
5.000 seconds
You create a tag that points to the Plant computer. In the tag’s Node
field, you assign the Plant_Computer node. In the tag’s Address field,
you enter
RejectCount
, which is the tag you want values for. The
information in the Address field is the OPC tag address.
When the RejectCount tag is used anywhere in the Supervisor
computer, it gets its value from the RejectCount tag in the Bottling
project on the Plant computer.
You can also write to the RejectCount tag in the Bottling project using
the RSView32 Set or = (Equal) commands (if writes are enabled in the
real-time data server on the Plant computer). The write will go
through to the programmable controller.
Connecting to RSLinx Gateway as a remote OPC
server
RSLinx
®
Gateway provides remote access to OPC clients, such as
RSView32, over a TCP/IP network. RSLinx Gateway supports up to
5 remote clients.
To use OPC with RSLinx Gateway, you must configure settings both
in RSLinx and in RSView32.
Configuring RSLinx Gateway
To use RSLinx Gateway, do the following in RSLinx:
configure RSLinx Gateway with drivers for each control network
RSLinx is connected to
create a DDE/OPC topic for each PLC on each control network