beautypg.com

Softlogix 5 addressing syntax, Softlogix 5 i/o and status files – Rockwell Automation 9301 Series RSView32 Users Guide User Manual

Page 724

background image

D–26

RSView32 User’s Guide

SoftLogix 5 addressing syntax

This section provides addressing syntax for SoftLogix 5 controllers.

SoftLogix 5 I/O and status files

F:eee/bb

F

File type:
I = Input
O = Output
S = Status

eee

Element number:
For I/O files: 0 – 277 octal
For status files: 0 – 511 decimal

bb

(optional)

Bit offset within word:
For I/O files: 0 – 17 octal
For status files: 0 – 15 decimal

Example: O:167/11