beautypg.com

Suppresson

Page 679

background image

RSView32 commands

A–59

SuppressOn

SuppressOn

Suppresses reporting of alarms for the specified tag.

The name of a tag, or a wildcard.

This command is useful when equipment repairs or maintenance
would otherwise result in alarms being generated. All alarms for each
threshold of the monitored tag are suppressed. Alarm suppression can
take place before or after issuing the AlarmOn command.

Toggle

Toggle [/V]

Reads the tag’s value and writes back a 1 or 0 as follows:

if the tag value is 0, Toggle changes it to 1

if the value is not 0, Toggle changes it to 0

[/V]

Performs a read immediately after the write to verify
that the value was altered in the programmable
controller or server.

This parameter is useful if the network is in poor
condition or susceptible to noise interference.

If the verification fails, the error message is logged to
the activity log, activity bar, or printer using the Tag
Write category. Specify where to send Tag Write
errors using the Categories tab of the Activity Log
Setup editor.

<tag_name>

The name of an analog or digital tag.