beautypg.com

Plc–5 i/o and status files – Rockwell Automation 9301 Series RSView32 Users Guide User Manual

Page 704

background image

D–6

RSView32 User’s Guide

PLC–5 I/O and status files

F:ee/bb

F

File type:
O = Output
I = Input
S = Status

ee

Element number:
For I/O files:
PLC–5/10: 0 – 037 octal
PLC–5/12: 0 – 037 octal
PLC–5/15: 0 – 037 octal
PLC–5/25: 0 – 077 octal
For status files: 0 – 31 decimal

bb

(optional)

Bit offset within word:
For I/O files: 0 – 17 octal
For status files: 0 – 15 decimal

Example: O:64/17