Running your project

18–7

Communication Status

Logs communication errors to the activity log file and/or the
activity bar if you set the project up to do this. To set this up, open
the Activity Log Setup editor and ensure the Log File and Activity
Bar check boxes are selected for the Communications category.

OPC/DDE Server

Enables RSView32 as an OPC

®

and DDE server. This is the same

as using the RTDataServerOn command.

Data Logging

Starts running the specified data log model. This is the same as
using the DataLogOn command. Up to 20 data log model files can
run simultaneously, but only one can be specified in the Startup
editor. To run more files, list them in a startup macro.

Global Key File

Runs the specified global key file. This is the same as using the Key
<file> command.

Derived Tags

Runs the specified derived tags file. This is the same as using the
DerivedOn <file> command. Up to 20 derived tag files can run
simultaneously, but only one can be specified in the Startup editor.
To run more files, list them in a startup macro.

Event Detector

Runs the specified event file. This is the same as using the
EventOn <file> command. Up to 20 event files can run
simultaneously, but only one file can be specified in the Startup
editor. To run more files, list them in a startup macro.

Startup Macro

Runs the specified macro. A startup macro allows you to run a
series of commands when the project starts. Any macro can be
used as a startup macro.