RSView32 commands

A–15

<EventType>

The type of alarm transaction, which must be one of
the following:

[IntoAlarm] Indicates that the tag has gone into
or [In]

alarm.

[OutOfAlarm]Indicates that the tag has gone out
or [Out]

of alarm.

[InAndOut

Indicates that an alarm has occurred,

OfAlarm]

but the tag is again immediately out of

or

alarm, such as a digital change–of–

[InAndOut] state alarm.

[TagType]

The type of tag which must be one of:

[/A]

Analog

[/D]

Digital

If you don’t specify either /A or /D, the alarm is
assumed to be analog.

[/VTagValue]

A floating–point value associated with the alarm
event. If the floating–point value is not specified, the
tag value is 0.0.

If the name of an alarm event is the name of a tag in
the tag database, the value specified by this parameter
will not update the tag’s value in the value table.

[/SSeverity]

The alarm severity. The severity is an integer from 1
to 8. Alarm severity can be specified only for alarm
events of type IntoAlarm, or InAndOutOfAlarm. If
a value is not specified, the alarm severity is 1.

[/HTime–

The time stamp associated with the alarm

stamp]

transaction, in the format:[Date]: