Configuring rsview32 for use with rslinx gateway – Rockwell Automation 9301 Series RSView32 Users Guide User Manual
Page 602

17–10
RSView32 User’s Guide
enable RSLinx Gateway
For information about configuring RSLinx Gateway, see the
documentation supplied with RSLinx.
Configuring RSView32 for use with RSLinx
Gateway
To use RSLinx Gateway with RSView32, do the following in
RSView32:
use the RSLinxOPCRemote program provided on the RSLinx CD
to register the RSLinx Gateway on the computer on which
RSView32 is installed.
in the Node editor, set up a remote OPC node for each PLC. For
more information about setting up an OPC node, see page 3-5.
create tags. For more information about creating tags, see
At runtime, use the same login name and password for the computer
running RSLinx Gateway and for the computer running RSView32. If
this is not practical, on the computer running RSLinx configure
DCOM to grant the RSView32 user access to the RSLinx computer.
For more information about configuring DCOM, see the Help
supplied with the DCOMCNFG utility.
Example: Configuring an OPC node for RSLinx Gateway
The following example describes how to create a node to connect to
RSLinx Gateway as a remote OPC server.
Server Name:
RSLinx OPC Server
or
RSLinx Remote OPC Server
If you are using RSLinx 2.0, the driver name is
RSLinx OPC Server. If you are using RSLinx 2.1, the