SLC addressing syntax

This section provides addressing syntax for these types of
programmable controllers:

SLC 5, which includes the fixed I/O SLC 5, SLC 5/01,

SLC 5/02, and SLC 5/03 (OS300)

SLC 5 (Enhanced), which includes the SLC 5/03 (OS 301),

SLC 5/04, and SLC 5/05

SLC 5 I/O files

F:ss.www/bb

F

File type:
I = Input
O = Output

ss

I/O slot number: 0 – 30 decimal

www

(optional)

I/O word number expansion: 0 – 255 decimal

bb

(optional)

Bit offset within word: 0 – 15 decimal
When input slot is 0: 0 – 23 decimal

Example: I:22.254/13

Important information for addressing

SLC 5 I/O modules

The RSView32

I/O module addressing system differs from the

corresponding ControlView

, APS, A.I.

500, and RSLogix 5

or

RSLogix 500

addressing systems. The RSView32 I/O data section

addressing does not match the physical slot of the I/O module.

Writing to the output files of an SLC 5 is not recommended.
However, if you do, be sure the SLC is not in RUN mode. If it is in
RUN mode, the write will fail and an error message will be logged to
the activity log file.